Section 10 (State chart): replace invented opening/closing/closed states with the real shared FSM states (accelerating/decelerating for moves; idle/starting/ warmingup/operational/stopping/coolingdown/emergencystop/off/maintenance for lifecycle). Show all valid transitions from stateConfig.json allowedTransitions. Document protected transitions (warmingup, coolingdown) and valve-specific pre-shutdown ramp-to-zero behaviour. Section 9 (Config): add missing editor fields from nodeClass.buildDomainConfig (startup/warmup/shutdown/cooldown times, speed, serviceType, fluidDensity, fluidTemperatureK, gasChokedRatioLimit). Correct config paths to match actual stateConfig / runtimeOptions split. Section 7 (Lifecycle): add FSM state labels to sequence diagram; show accelerating → operational final step. Sections 2/6/12/14: minor precision improvements (Port-2 note, abort-deadlock recipe, execSequence Phase-7 removal warning). Re-ran npm run wiki:all; AUTOGEN blocks intact. Co-Authored-By: Claude Sonnet 4.6 <noreply@anthropic.com>
16 KiB
valve
Reflects code as of
e27135b· regenerated2026-05-11vianpm run wiki:allIf this banner is stale, the page may be out of date. Treat as informative, not authoritative.
1. What this node is
valve models a single actuated throttling valve at the S88 Equipment Module level. It loads a supplier Kv-vs-position characteristic curve, drives an FSM for open/close move sequences (using accelerating/decelerating states shared with rotatingMachine), and recomputes pressure drop from flow + Kv via a hydraulic model. Used standalone or as a child of valveGroupControl.
2. Position in the platform
flowchart LR
vgc[valveGroupControl<br/>Unit]:::unit -->|set.position| this[valve<br/>Equipment]:::equip
src["machine / MGC / PS<br/>(upstream source)"]:::unit -->|child.register| this
meas[measurement<br/>type=pressure / flow]:::ctrl -.->|data| this
this -->|child.register Port 2| vgc
this -->|evt.deltaPChange| vgc
this -->|evt.fluidCompatibilityChange| vgc
classDef unit fill:#50a8d9,color:#000
classDef equip fill:#86bbdd,color:#000
classDef ctrl fill:#a9daee,color:#000
S88 colours: Unit #50a8d9, Equipment #86bbdd, Control Module #a9daee. Source: .claude/rules/node-red-flow-layout.md.
3. Capability matrix
| Capability | Status | Notes |
|---|---|---|
| Predicts deltaP from flow + Kv | ✅ | Hydraulic model picks liquid vs gas formula per serviceType. |
| Loads supplier curve by model name | ✅ | asset.model resolved through loadModel; inline valveCurve override supported. |
| Position move FSM | ✅ | accelerating / decelerating states with interruptible setpoints; moveTo uses shared state machine. |
| Startup / shutdown sequences | ✅ | Pre-shutdown ramps valve to position 0 before executing stop sequence. |
| Emergency-stop sequence | ✅ | cmd.estop → emergencystop → off sequence. |
| Fluid-contract aggregation | ✅ | Tracks upstream service type via registered sources through FluidCompatibility. |
| Gas-choke detection | ⚠️ | Hard cap at gasChokedRatioLimit; surfaced in hydraulicDiagnostics. |
| Multi-parent registration | ⚠️ | Allowed but not exercised in production tests. |
4. Code map
flowchart TB
subgraph nodeRED["nodeClass.js — adapter (BaseNodeAdapter)"]
nc["buildDomainConfig()<br/>static DomainClass=Valve, commands<br/>tickInterval=null (event-driven)"]
end
subgraph domain["specificClass.js — orchestrator (BaseDomain)"]
sc["Valve.configure()<br/>wires concern modules<br/>overrides registerChild → FluidCompatibility"]
end
subgraph concerns["src/ concern modules"]
state["state/<br/>stateBindings → positionChange"]
fluid["fluid/<br/>FluidCompatibility"]
curve["curve/<br/>SupplierCurvePredictor"]
meas["measurement/<br/>MeasurementRouter + FORMULA_UNITS"]
flow["flow/<br/>FlowController (setpoint, sequences)"]
io["io/<br/>buildOutput + buildStatusBadge"]
hyd["hydraulicModel.js<br/>ValveHydraulicModel"]
end
nc --> sc
sc --> state
sc --> fluid
sc --> curve
sc --> meas
sc --> flow
sc --> io
sc --> hyd
| Module | Owns | Read first if you're changing… |
|---|---|---|
state/ |
Bindings from state-machine positionChange → updatePosition() |
Move-finished triggers, position callbacks. |
fluid/ |
Service-type compatibility, contract aggregation | Gas-vs-liquid mismatch warnings, upstream fluid tracking. |
curve/ |
Supplier Kv curve load + interpolation | Curve fitting, model selection, density keys. |
measurement/ |
Pressure/flow routing + deltaP recompute | What triggers a recalc, measurement container writes. |
flow/ |
Sequence + setpoint execution, mode validation | Startup / shutdown / move semantics, allowed-source checks. |
io/ |
Port-0 output shape + status badge | What lands on the wire each tick. |
hydraulicModel.js |
Liquid + gas deltaP formulas, choke detection | Hydraulic calculation errors, choke ratio behaviour. |
5. Topic contract
Auto-generated from
src/commands/index.js. Do NOT hand-edit between the markers. Re-runnpm run wiki:contract.
| Canonical topic | Aliases | Payload | Unit | Effect |
|---|---|---|---|---|
set.mode |
setMode |
string |
— | Switch the valve between auto / manual control modes. |
cmd.startup |
(none) | any |
— | Initiate the valve startup sequence. |
cmd.shutdown |
(none) | any |
— | Initiate the valve shutdown sequence. |
cmd.estop |
emergencystop, emergencyStop |
any |
— | Trigger an emergency stop on the valve. |
execSequence |
(none) | object |
— | Legacy umbrella that demuxes payload.action to startup / shutdown / estop. |
set.position |
execMovement |
object |
— | Move the valve to a control-% position via execMovement. |
data.flow |
updateFlow |
object |
— | Push a measured flow into the valve (variant + position + unit). |
query.curve |
showcurve |
any |
— | Return the valve characteristic curve on the reply port. |
child.register |
registerChild |
string |
— | Register a child measurement with this valve. |
6. Child registration
valve overrides BaseDomain.registerChild with FluidCompatibility.registerChild. Upstream sources feed the fluid-contract aggregator; measurement children attach through the standard measurement handshake and land in MeasurementRouter.
flowchart LR
subgraph kids["accepted children (softwareType)"]
src["machine / rotatingmachine<br/>machinegroup / pumpingstation<br/>valvegroupcontrol"]:::unit
m["measurement<br/>type=pressure or flow"]:::ctrl
end
src -->|getFluidContract| fluid[FluidCompatibility<br/>aggregates serviceType]
m -->|"<type>.measured.<position>"| router[MeasurementRouter<br/>updatePressure / updateFlow]
router --> deltaP[updateDeltaP<br/>writes pressure.predicted.delta]
fluid --> evt1["evt.fluidCompatibilityChange<br/>evt.fluidContractChange"]
deltaP --> evt2[evt.deltaPChange]
classDef unit fill:#50a8d9,color:#000
classDef ctrl fill:#a9daee,color:#000
| softwareType | onRegister side-effect | Subscribed events |
|---|---|---|
machine / rotatingmachine |
Stored as upstream source; reads getFluidContract() or defaults to liquid. |
fluidContractChange |
machinegroup / machinegroupcontrol |
Same; recomputes aggregate service type. | fluidContractChange |
pumpingstation |
Same. | fluidContractChange |
valvegroupcontrol |
Same. | fluidContractChange |
measurement |
Routed via measurement handshake; values land in MeasurementContainer. |
<type>.measured.<position> |
7. Lifecycle — what one event does
sequenceDiagram
participant parent as valveGroupControl
participant valve as valve
participant fsm as state FSM
participant hyd as hydraulicModel
participant out as Port-0
parent->>valve: set.position { setpoint: 60 }
valve->>fsm: moveTo(60)
fsm-->>fsm: operational → accelerating
fsm-->>valve: positionChange ticks (stateBindings)
valve->>valve: predictKv(position)
valve->>hyd: calculateDeltaPMbar(q, kv, downP, rho, T)
hyd-->>valve: { deltaPMbar, diagnostics }
valve->>valve: write pressure.predicted.delta
valve->>parent: emitter.emit('deltaPChange', deltaP)
valve->>out: msg { topic, payload (delta-compressed) }
fsm-->>fsm: accelerating → operational (setpoint reached)
8. Data model — getOutput()
What lands on Port 0. Composed in io/output.buildOutput, then delta-compressed by outputUtils.formatMsg.
| Key | Type | Unit | Sample |
|---|---|---|---|
state |
string | — | "operational" |
percentageOpen |
number | % | 0 |
moveTimeleft |
number | s | 0 |
mode |
string | — | "auto" |
downstream_predicted_flow |
number | m3/h | 0 |
downstream_measured_flow |
number | m3/h | (emitted when measurement child present) |
downstream_predicted_pressure |
number | mbar | (emitted when upstream pressure present) |
downstream_measured_pressure |
number | mbar | (emitted when measurement child present) |
delta_predicted_pressure |
number | mbar | 0 |
Measurement keys follow the legacy <position>_<variant>_<type> shape (e.g. downstream_predicted_flow, delta_predicted_pressure). Only keys with finite values are emitted — consumers must cache and merge (delta-compression is active).
9. Configuration — editor form ↔ config keys
flowchart TB
subgraph editor["Node-RED editor form"]
f1[Reaction Speed]
f2[Asset model / supplier / category]
f3[Service type]
f4[Fluid density / temperature K]
f5[Gas choke ratio limit]
f6[Startup / warmup / shutdown / cooldown times]
f7[Log level / enableLog]
f8[positionVsParent]
end
subgraph config["Domain config slice"]
c1["movement.speed (stateConfig)"]
c2[asset.model]
c3["runtimeOptions.serviceType → hydraulicModel"]
c4["runtimeOptions.fluidDensity / fluidTemperatureK"]
c5["runtimeOptions.gasChokedRatioLimit"]
c6["stateConfig.time.starting / warmingup / stopping / coolingdown"]
c7["general.logging.enabled / logLevel"]
c8["functionality.positionVsParent → Port-2 registration"]
end
f1 --> c1
f2 --> c2
f3 --> c3
f4 --> c4
f5 --> c5
f6 --> c6
f7 --> c7
f8 --> c8
| Form field | Config path | Default | Range / type | Where used |
|---|---|---|---|---|
| Reaction Speed | movement.speed (stateConfig) |
1 |
> 0 (%/s) | MovementManager — sets rate of position change |
| Asset model | asset.model |
'Unknown' |
string | SupplierCurvePredictor — selects Kv curve dataset |
| Service type | runtimeOptions.serviceType |
null (from asset) |
'gas' / 'liquid' |
ValveHydraulicModel formula selection |
| Fluid density | runtimeOptions.fluidDensity |
model default | > 0 (kg/m³) | liquid hydraulic formula |
| Fluid temperature | runtimeOptions.fluidTemperatureK |
model default | > 0 (K) | gas hydraulic formula |
| Gas choke limit | runtimeOptions.gasChokedRatioLimit |
per asset | 0–1 | gas choke cap in ValveHydraulicModel |
| Startup time | stateConfig.time.starting |
10 s |
> 0 (s) | StateManager transition timer |
| Warmup time | stateConfig.time.warmingup |
5 s |
> 0 (s) | StateManager protected transition |
| Shutdown time | stateConfig.time.stopping |
5 s |
> 0 (s) | StateManager transition timer |
| Cooldown time | stateConfig.time.coolingdown |
10 s |
> 0 (s) | StateManager transition timer |
| Mode | mode.current |
'auto' |
auto / virtualControl / fysicalControl / maintenance |
FlowController.isValidSourceForMode |
| Log level | general.logging.logLevel |
'info' |
enum | structured logger |
| positionVsParent | functionality.positionVsParent |
'atEquipment' |
enum | Port-2 registration message to parent |
10. State chart
stateDiagram-v2
[*] --> off
off --> idle : cmd.startup (boot sequence)
off --> emergencystop : cmd.estop
off --> maintenance : set.mode=maintenance
idle --> starting : cmd.startup
idle --> off : (direct transition)
idle --> emergencystop : cmd.estop
idle --> maintenance : set.mode=maintenance
starting --> warmingup : timed (starting duration)
starting --> emergencystop : cmd.estop
warmingup --> operational : timed (warmup duration) [protected — cannot abort]
warmingup --> emergencystop : cmd.estop
operational --> accelerating : set.position > current
operational --> decelerating : set.position < current
operational --> stopping : cmd.shutdown
operational --> emergencystop : cmd.estop
accelerating --> operational : setpoint reached
accelerating --> emergencystop : cmd.estop
decelerating --> operational : setpoint reached
decelerating --> emergencystop : cmd.estop
stopping --> coolingdown : timed (stopping duration)
stopping --> idle : (direct)
stopping --> emergencystop : cmd.estop
coolingdown --> idle : timed (cooldown duration) [protected — cannot abort]
coolingdown --> off : (direct)
coolingdown --> emergencystop : cmd.estop
emergencystop --> idle : cmd.reset / sequence
emergencystop --> off : cmd.reset / sequence
emergencystop --> maintenance : (allowed)
maintenance --> idle : manual reset
maintenance --> off : manual reset
Key valve-specific behaviours:
accelerating= position moving up;decelerating= position moving down. Both firepositionChangeticks. The valve'sstateBindingshooks these toupdatePosition()→ Kv lookup → deltaP recompute.warmingupandcoolingdownare protected — the abort signal is disabled; these phases cannot be interrupted.cmd.shutdownfromoperationalfirst ramps the valve to position 0 (viaFlowController.executeSequence('shutdown')), then transitionsstopping → coolingdown → idle.cmd.estoptriggersemergencystop → offregardless of current state (except from within protected transitions).- Default sequences:
startup=[starting, warmingup, operational];boot=[idle, starting, warmingup, operational];emergencystop=[emergencystop, off].
11. Examples
| Tier | File | What it shows | Mandatory? |
|---|---|---|---|
| Basic | examples/basic.flow.json |
Inject set.position + minimal wiring, no parent |
✅ |
| Integration | examples/integration.flow.json |
valve + VGC + upstream measurement source | ✅ |
| Edge | examples/edge.flow.json |
Edge-case inputs (gas, choke, estop, bad setpoints) | ⭕ optional |
Renamed example files (01-Basic.flow.json, 02-Integration.flow.json, 03-Dashboard.flow.json) will replace the above when produced. Screenshots under wiki/_partial-screenshots/valve/. Docker compose snippet under examples/README.md.
12. Debug recipes
| Symptom | First thing to check | Where to look |
|---|---|---|
Status badge shows ⚠ no input |
Did any pressure / flow measurement register? Watch Port 2. | Debug tap on Port 2 |
delta_predicted_pressure stuck at 0 |
Is kv > 0? FSM may be in off / idle — valve is closed. |
state.getCurrentState(), percentageOpen |
| Gas mismatch warning on status badge | fluidCompatibility.status is mismatch or conflict. |
getFluidCompatibility() |
query.curve returns empty curve |
asset.model not found by loadModel; check SupplierCurvePredictor.snapshot(). |
SupplierCurvePredictor.snapshot() |
| deltaP non-finite | Downstream gauge pressure absolute term ≤ 0, or choked ratio reached. | hydraulicDiagnostics in output |
set.position has no effect |
Check currentMode — source may not be in mode.allowedSources[mode]. |
FlowController.isValidSourceForMode |
FSM stuck in accelerating / decelerating |
Movement was aborted but _returnToOperationalOnAbort was false. Send a new set.position. |
state.js abort logic |
Never ship
enableLog: 'debug'in a demo — fills the container log within seconds and obscures real errors. Use only for live debugging.
13. When you would NOT use this node
- Use valve for a throttling actuator with a known Kv curve. For a fixed-restriction orifice (no actuator, no curve), model the deltaP externally.
- Don't use valve to model a non-return / check valve — no position control or FSM-driven actuation is exposed.
- Skip valve when an upstream source already provides flow directly and no pressure-drop estimate is needed — wire the source straight to the parent without inserting a valve.
14. Known limitations / current issues
| # | Issue | Tracked in |
|---|---|---|
| 1 | Gas-choke detection is a hard cap, not a smooth transition — chart traces show a step at the choked-ratio limit. | hydraulicModel.js |
| 2 | Multi-parent registration is allowed but not exercised in production tests. | CONTRACT.md — Children registered by this node |
| 3 | set.position move sequences are interruptible but tests cover happy-path only; abort-deadlock edge case documented separately. |
state.js abort logic + test/integration/ |
| 4 | execSequence (legacy umbrella topic) will be removed in Phase 7 — callers must migrate to cmd.startup / cmd.shutdown / cmd.estop. |
CONTRACT.md — execSequence demux |