e041877ae43d3b2a8781e13c0e0e3bb54a000bf5
Reverts the canonical half of 8216480 (which set BOTH canonical and output
to m³/h) back to the platform-wide m³/s convention. Canonical m³/s is what
every cross-node consumer assumes — MGC percent→flow demand interpolation,
the volume integrator (flow × dt), and physics-sanity balances. Changing the
canonical basis to m³/h silently scaled those by 3600×.
Output flow / netFlowRate stay m³/h so telemetry and dashboard series remain
on the same axis as the rest of the pump group (verified slice #47). The
m³/s→m³/h conversion now happens at the output boundary only, never on the
internal integrator basis.
No smoothing/hysteresis added for the PS→MGC demand hunting: per design
review that belongs in a dedicated intermediate node (e.g. a PID), not in
the pumpingStation or machineGroupControl control path.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
pumpingStation
Wet-well basin model and pump orchestration node for EVOLV.
The detailed documentation lives in wiki/:
wiki/functional-description.mddefines the shared basin model, pipe reference semantics, safety points, net-flow selection, and child registration behaviour.wiki/modes/documents control-mode-specific behaviour. For v1.0 the editor exposeslevelbasedandmanual; levelbased supports linear and log curves with separate rising/falling ramp semantics.wiki/diagrams/basin-model.drawio.svgis the current source of truth for the generic basin model.examples/basic-dashboard.flow.jsonprovides a simple Node-RED Dashboard 2 flow with level, volume, demand, net-flow, and safety-state trends.
Description