Files
pumpingStation/src
znetsixe e041877ae4 fix(ps): keep canonical flow in m³/s, emit output in m³/h
Reverts the canonical half of 8216480 (which set BOTH canonical and output
to m³/h) back to the platform-wide m³/s convention. Canonical m³/s is what
every cross-node consumer assumes — MGC percent→flow demand interpolation,
the volume integrator (flow × dt), and physics-sanity balances. Changing the
canonical basis to m³/h silently scaled those by 3600×.

Output flow / netFlowRate stay m³/h so telemetry and dashboard series remain
on the same axis as the rest of the pump group (verified slice #47). The
m³/s→m³/h conversion now happens at the output boundary only, never on the
internal integrator basis.

No smoothing/hysteresis added for the PS→MGC demand hunting: per design
review that belongs in a dedicated intermediate node (e.g. a PID), not in
the pumpingStation or machineGroupControl control path.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-05-27 18:31:39 +02:00
..