Files
pumpingStation/test/basic/_probe_upstream_emit.test.js
znetsixe 2e4ad8d3f1 fix(levelBased): drop hold zone, route through MGC.setDemand, add holdLevel + integrator variant pick; slim npm pack
levelBased ramp + engagement:
- Ramp foot is now max(startLevel, holdLevel) — was max(startLevel,
  inflowLevel). inflowLevel is basin geometry, not a control setpoint;
  the implicit hold zone it created was causing pumps to "start at
  inflowLevel" instead of startLevel.
- New optional `holdLevel` config (defaults to startLevel = no hold band).
  When raised, pumps engage at startLevel and hold at 0 % = MGC flow.min
  across [startLevel, holdLevel], then ramp 0..100 % to maxLevel.
- Engagement decided in run() (not in `_applyMachineGroupLevelControl`):
  rising-edge hysteresis arming gates a clean turnOff early-return.
  Once armed, the helper always forwards setDemand(pct, '%') — 0 %
  legitimately means "engaged at min flow", no more soft-turnOff at
  the boundary.
- Disengagement paths (minLevel hard-stop, stopLevel falling-edge,
  pre-arming idle) now all clear the shifted-ramp hysteresis state too.
- Threshold validator drops the startLevel ≤ inflowLevel rule; adds
  startLevel ≤ holdLevel < maxLevel (only checked when holdLevel is
  explicitly set, so default-null doesn't false-flag).

MGC unit math:
- Replace direct group.handleInput(percent) with group.setDemand(pct, '%')
  in _applyMachineGroupLevelControl. The percent → m³/s resolution now
  lives in MGC.setDemand (committed separately in the MGC submodule).

FlowAggregator variant picking:
- New _pickFlowSum() helper mirrors selectBestNetFlow's variant
  precedence (measured first, then predicted) and resolves each side
  independently. Realistic mixed case — real measured upstream sensor +
  predicted pump outflow — now feeds the predicted-volume integrator.
  Was reading only `flow.predicted.*` so a real upstream sensor
  (which writes `flow.measured.*`) never moved the level.

Editor:
- New `holdLevel` and `deadZoneKeepAlivePercent` defaults + side-panel
  input rows in the levelbased mode preview.
- Add the missing `ps-mode-line-holdLevel` SVG marker (was declared in
  the side-panel coupling but the SVG element didn't exist, so the
  dashed line never rendered).
- Relax stopLevel marker gate so it renders for any non-negative typed
  value — start/stop ordering is the ribbon's job, not the marker's
  (was hiding the line whenever startLevel was momentarily smaller).
- Add holdLevel to the marker loop in mode-preview so changes track.
- Add stopLevel + holdLevel + maxLevel to all three bindRedraw lists
  (basin-diagram, mode-preview, bounds.apply) so the SVG, validation
  ribbon, and HTML5 min/max attrs update on every edit.
- Initialise stopLevel + holdLevel + deadZoneKeepAlivePercent inputs
  in oneditprepare so reopening the editor shows the saved values.
- nodeClass passes holdLevel + deadZoneKeepAlivePercent into the
  domain config.

Tests:
- New test/basic/_probe_upstream_emit.test.js: confirms the parent
  surfaces flow.measured.upstream.* on Port 0 after a measurement
  child write — pins the previously-invisible measured variant flow.
- flowAggregator.basic.test.js: two new regression cases — measured
  inflow when predicted side is empty, and the measured-in /
  predicted-out mixed case.
- control-levelBased.basic.test.js: new cases for the holdLevel hold
  band, the [stopLevel, startLevel] keep-alive, the engagement gate,
  and the "0 % at startLevel = setDemand" contract.
- specificClass.test.js: zone tests adjusted to the new ramp foot.
  Shifted-ramp tests pin holdLevel = 3 explicitly so their legacy
  arithmetic (ramp foot at inflowLevel) stays self-consistent.
- shifted-ramp-end-to-end.test.js: same holdLevel pin for the same
  reason.

Packaging:
- Add .gitignore + .npmignore so the published tarball drops the
  wiki/, simulations/, test/, tools/, .claude/ etc. The pack went
  from 1.5 MB (72 files) to ~57 KB (30 files).

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-05-19 21:36:29 +02:00

86 lines
3.3 KiB
JavaScript

// Throwaway probe — exercises the exact path:
// measurement child writes flow.measured.upstream → pumpingStation parent
// subscribes → getOutput() (≡ what Port 0 emits).
// Run with: node --test test/basic/_probe_upstream_emit.test.js
const test = require('node:test');
const assert = require('node:assert/strict');
const PumpingStation = require('../../src/specificClass');
const { MeasurementContainer, configManager } = require('generalFunctions');
const EventEmitter = require('node:events');
// Minimal PumpingStation config — matches the editor defaults shape.
function makePsConfig() {
const ui = {
name: 'PS', basinVolume: 50, basinHeight: 5,
inflowLevel: 3, outflowLevel: 0.2, overflowLevel: 4.5,
minHeightBasedOn: 'outlet',
controlMode: 'levelbased',
minLevel: 1, startLevel: 2, maxLevel: 4,
levelCurveType: 'linear',
processOutputFormat: 'process', dbaseOutputFormat: 'influxdb',
};
const cm = new configManager();
// Use the same buildConfig pipeline the runtime uses.
return cm.buildConfig('pumpingStation', ui, 'ps-probe', {
basin: {
volume: 50, height: 5, inflowLevel: 3, outflowLevel: 0.2, overflowLevel: 4.5,
},
hydraulics: { minHeightBasedOn: 'outlet' },
control: {
mode: 'levelbased',
allowedModes: new Set(['levelbased']),
levelbased: { minLevel: 1, startLevel: 2, maxLevel: 4, curveType: 'linear' },
},
safety: {},
});
}
// Fake measurement child that looks exactly like the real one to the router:
// - softwareType 'measurement'
// - config.asset.type = 'flow'
// - config.functionality.positionVsParent = 'upstream'
// - .measurements is a real MeasurementContainer with a real emitter
function makeMeasurementChild(id = 'meas-probe') {
const measurements = new MeasurementContainer({
autoConvert: true,
preferredUnits: { flow: 'm3/s' },
});
// Real container ships an emitter; sanity check.
assert.ok(measurements.emitter instanceof EventEmitter || typeof measurements.emitter?.on === 'function');
return {
id,
source: {
config: {
general: { id, name: id },
functionality: { softwareType: 'measurement', positionVsParent: 'upstream' },
asset: { type: 'flow' },
},
measurements,
},
};
}
test('PROBE: measurement child writes flow.measured.upstream — parent surfaces it on getOutput()', () => {
const ps = new PumpingStation(makePsConfig());
const child = makeMeasurementChild();
// Register the child the same way the runtime does.
ps.childRegistrationUtils.registerChild(child.source, 'upstream');
// Drive a value through the child's MeasurementContainer the way Channel
// does — type/variant/position chain then .value().
child.source.measurements
.type('flow').variant('measured').position('upstream')
.value(12, Date.now(), 'm3/h'); // 12 m³/h ≈ 0.00333 m³/s
const out = ps.getOutput();
const upstreamKeys = Object.keys(out).filter((k) => k.startsWith('flow.measured.upstream'));
console.log('flow.measured.upstream.* keys in Port 0 payload:', upstreamKeys);
for (const k of upstreamKeys) console.log(` ${k} = ${out[k]}`);
// The contract: the parent should surface the upstream measurement.
assert.ok(upstreamKeys.length > 0, 'parent must surface flow.measured.upstream.* on Port 0');
});