znetsixe dfaa0c3ae8 feat(pumpingstation): warn when control engages with no machine group registered
A station engaged above startLevel computes a real demand, but if no machine
group is registered (e.g. the Port 2 parent↔group registration was dropped by a
partial redeploy) the demand is silently forwarded nowhere and the pumps never
react — invisible to the operator. levelBased now warns once when engaged with
an empty machineGroups map (throttled via host._warnedNoMachineGroup, re-arms
when a group reappears); manual.forwardDemand warns when neither a group nor a
direct machine is registered.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-05-27 10:58:34 +02:00

50 lines
1.7 KiB
JavaScript

async function run() {
// No-op: manual mode is event-driven via set.demand → forwardDemand,
// not tick-driven.
}
async function forwardDemand(ctx, demand) {
const { machineGroups, machines, unitPolicy, logger } = ctx;
logger?.info?.(`Manual demand forwarded: ${demand}`);
if (machineGroups && Object.keys(machineGroups).length > 0) {
const groupDemand = unitPolicy.convert(demand, 'm3/h', 'm3/s', 'manual demand to machineGroups');
await Promise.all(
Object.values(machineGroups).map((group) =>
group.handleInput('parent', groupDemand).catch((err) => {
logger?.error?.(`Failed to forward demand to group: ${err.message}`);
})
)
);
}
if (machines && Object.keys(machines).length > 0) {
const perMachine = demand / Object.keys(machines).length;
for (const machine of Object.values(machines)) {
try {
await machine.handleInput('parent', 'execMovement', perMachine);
} catch (err) {
logger?.error?.(`Failed to forward demand to machine: ${err.message}`);
}
}
}
// Neither a group nor a direct machine is registered, so the operator's
// demand silently goes nowhere. Surface it — the usual cause is a dropped
// Port 2 parent↔child registration after a partial redeploy.
const noGroups = !machineGroups || Object.keys(machineGroups).length === 0;
const noMachines = !machines || Object.keys(machines).length === 0;
if (noGroups && noMachines) {
logger?.warn?.(
`Manual demand ${demand} not forwarded — no machine group or machine is registered to this pumping station. `
+ `Check the parent↔child Port 2 registration (redeploy/restart fully to restore it).`
);
}
}
module.exports = {
name: 'manual',
run,
forwardDemand,
};