A station engaged above startLevel computes a real demand, but if no machine group is registered (e.g. the Port 2 parent↔group registration was dropped by a partial redeploy) the demand is silently forwarded nowhere and the pumps never react — invisible to the operator. levelBased now warns once when engaged with an empty machineGroups map (throttled via host._warnedNoMachineGroup, re-arms when a group reappears); manual.forwardDemand warns when neither a group nor a direct machine is registered. Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
50 lines
1.7 KiB
JavaScript
50 lines
1.7 KiB
JavaScript
async function run() {
|
|
// No-op: manual mode is event-driven via set.demand → forwardDemand,
|
|
// not tick-driven.
|
|
}
|
|
|
|
async function forwardDemand(ctx, demand) {
|
|
const { machineGroups, machines, unitPolicy, logger } = ctx;
|
|
logger?.info?.(`Manual demand forwarded: ${demand}`);
|
|
|
|
if (machineGroups && Object.keys(machineGroups).length > 0) {
|
|
const groupDemand = unitPolicy.convert(demand, 'm3/h', 'm3/s', 'manual demand to machineGroups');
|
|
await Promise.all(
|
|
Object.values(machineGroups).map((group) =>
|
|
group.handleInput('parent', groupDemand).catch((err) => {
|
|
logger?.error?.(`Failed to forward demand to group: ${err.message}`);
|
|
})
|
|
)
|
|
);
|
|
}
|
|
|
|
if (machines && Object.keys(machines).length > 0) {
|
|
const perMachine = demand / Object.keys(machines).length;
|
|
for (const machine of Object.values(machines)) {
|
|
try {
|
|
await machine.handleInput('parent', 'execMovement', perMachine);
|
|
} catch (err) {
|
|
logger?.error?.(`Failed to forward demand to machine: ${err.message}`);
|
|
}
|
|
}
|
|
}
|
|
|
|
// Neither a group nor a direct machine is registered, so the operator's
|
|
// demand silently goes nowhere. Surface it — the usual cause is a dropped
|
|
// Port 2 parent↔child registration after a partial redeploy.
|
|
const noGroups = !machineGroups || Object.keys(machineGroups).length === 0;
|
|
const noMachines = !machines || Object.keys(machines).length === 0;
|
|
if (noGroups && noMachines) {
|
|
logger?.warn?.(
|
|
`Manual demand ${demand} not forwarded — no machine group or machine is registered to this pumping station. `
|
|
+ `Check the parent↔child Port 2 registration (redeploy/restart fully to restore it).`
|
|
);
|
|
}
|
|
}
|
|
|
|
module.exports = {
|
|
name: 'manual',
|
|
run,
|
|