Files
pumpingStation/wiki/functional-description.md
znetsixe 4637448c49 Add modes/ section with levelbased page as the template
Introduces the pattern: basin model is the shared canvas (mode-agnostic
physics); each control mode is its own page under wiki/modes/ plus a
demand-vs-level transfer-function diagram under wiki/diagrams/modes/.

- wiki/modes/README.md — index + per-mode page template (inputs,
  threshold policy, demand formula, edge cases, related)
- wiki/modes/levelbased.md — first worked example using the new naming
  convention (dryRunLevel / minLevel / startLevel / maxLevel /
  overflowLevel). Forward-looking — the code still uses the old names
  until the pending rename refactor.
- wiki/diagrams/modes/levelbased.drawio.svg — transfer-function plot
  (zones: STOP / DEAD ZONE / RAMP / SATURATE, safety trips outside the
  plot). Round-trippable via embedded drawio XML.
- functional-description.md — replaced the inline levelbased/manual
  subsection with a table pointing at the modes/ pages. Removed the
  old control-zones ASCII diagram reference (superseded by the
  per-mode transfer function).
- wiki/README.md — added Control modes entry + diagrams/modes/ pointer.

The remaining placeholder modes (flowbased, pressureBased,
percentageBased, powerBased, hybrid, manual) can each fill in the
template independently.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-04-22 15:45:01 +02:00

332 lines
20 KiB
Markdown
Raw Blame History

This file contains ambiguous Unicode characters
This file contains Unicode characters that might be confused with other characters. If you think that this is intentional, you can safely ignore this warning. Use the Escape button to reveal them.
---
title: pumpingStation — Functional Description
node: pumpingStation
updated: 2026-04-22
status: draft
---
# pumpingStation — Functional Description
The `pumpingStation` node models an S88 **Process Cell**: a wet-well basin with inflow and outflow, wrapped around one or more pump controllers. Every second it recomputes the basin's water balance, picks the most trustworthy net-flow source, runs its safety interlocks, and finally commands its children (individual pumps, `machineGroupControl`, or nested pumping stations) so the level stays inside the safe operating band.
This page is the operator-facing reference, derived from [`src/specificClass.js`](../src/specificClass.js). For the 3-tier code layout see [EVOLV — Node Architecture](https://gitea.wbd-rd.nl/RnD/EVOLV/src/branch/main/wiki/architecture/node-architecture.md); for the atomic pump model see the [rotatingMachine wiki](https://gitea.wbd-rd.nl/RnD/rotatingMachine/wiki).
> **Diagrams on this page are editable.** Sources live in [`diagrams/`](diagrams/) — open the `.drawio` file in [draw.io](https://app.diagrams.net/), export to SVG, commit. See [`diagrams/README.md`](diagrams/README.md).
## At a glance
| Item | Value |
|---|---|
| Node category | EVOLV |
| S88 level | Process Cell (`#0c99d9`, lane L5) |
| Inputs | 1 (message-driven) |
| Outputs | 3 — `process` / `dbase` / `parent` |
| Tick period | 1 s |
| Basin model | Rectangular prismatic — `volume = level × surfaceArea` |
| Canonical units (internal) | Pa, m³/s, W, K, m, m³ |
| Control modes implemented | `levelbased`, `manual` (placeholders for `flowbased`, `pressureBased`, `percentageBased`, `powerBased`, `hybrid`) |
| Default flow dead-band | `1e-4 m³/s` (≈ 0.36 m³/h) |
## Lifecycle
1. **Construct.** The node merges the user's editor config over the schema defaults, creates the measurement store, and seeds the predicted volume at the basin's operational floor (`minVol`).
2. **Register children.** Sensors, pumps, machine groups, and nested stations register via the Port-2 handshake. The station subscribes only to the *highest-level aggregator* for predicted flow to avoid double-counting (MGC if present, otherwise the individual pump).
3. **Tick loop (1 s).** `_updatePredictedVolume → _selectBestNetFlow → _safetyController → _controlLogic → state snapshot → output`.
## Editor configuration
Every field on the pumpingStation editor maps directly to the config schema in `generalFunctions/src/configs/pumpingStation.json`.
### Basin geometry (section `basin`)
| Field | Default | Meaning |
|---|---|---|
| **Basin Volume (m³)** | `1` | Total geometric volume of the empty basin (floor to rim). |
| **Basin Height (m)** | `1` | Physical wall height from floor to rim. |
| **Inlet Elevation (m)** | `2` | Centre of the inlet pipe, measured from the floor. |
| **Outlet Elevation (m)** | `0.2` | Centre of the pump-suction pipe, measured from the floor. |
| **Overflow Level (m)** | `2.5` | Overflow-weir crest, measured from the floor. Above this → overfill safety. |
Constant cross-section is assumed: `surfaceArea = volume / height`. All derived volumes (`minVolOut`, `minVolIn`, `maxVolOverflow`, `maxVol`) are computed once in `initBasinProperties()` and kept on `station.basin`.
### Hydraulics (section `hydraulics`)
| Field | Default | Meaning |
|---|---|---|
| **Minimum Height Based On** | `outlet` | `outlet``minVol = heightOutlet × area` (includes the buffer). `inlet``minVol = heightInlet × area` (buffer treated as unavailable). |
| **Reference Height** | `NAP` | Vertical datum: `NAP` / `EVRF` / `EGM2008`. Metadata only — not used in math today. |
| **Basin Bottom (m Refheight)** | `0` | Absolute elevation of the basin floor, for cross-basin comparisons. |
### Control (section `control`)
| Field | Default | Meaning |
|---|---|---|
| **Control mode** | `levelbased` | Active control strategy. Schema enumerates seven modes; today `levelbased` is fully implemented, `manual` forwards demand via `Qd`, others are placeholders. |
| **startLevel (m)** | `1` | At or below this level, the station is in the DEAD ZONE — pumps stay in their last state. |
| **stopLevel (m)** | `1` | Below this level → unconditional MGC shutdown. |
| **Min flow (m)** | `1` | Bottom of the linear scaling range (0 % demand). Should equal `startLevel`. |
| **Max flow (m)** | `4` | Top of the linear scaling range (100 % demand). Typically ≈ `heightOverflow`. |
| **Flow setpoint** | `0` | Flow-based target (m³/h). Placeholder until `flowbased` is wired. |
| **Deadband** | `0` | Flow-based deadband (m³/h). Placeholder. |
### Safety (section `safety`)
| Field | Default | Meaning |
|---|---|---|
| **Time To Empty/Full (s)** | `0` | If > 0, triggers safety when predicted time-to-overflow or time-to-empty falls below this value. `0` disables time-based protection. |
| **Enable Dry-Run Protection** | `true` | If on, pumps are shut down once volume drops below the dry-run threshold while draining. |
| **Low Volume Threshold (%)** | `2` | Dry-run trigger: `triggerLowVol = minVol × (1 + pct/100)`. |
| **Enable Overfill Protection** | `true` | If on, upstream inflows are shut down once volume climbs above the overfill threshold while filling. |
| **High Volume Threshold (%)** | `98` | Overfill trigger: `triggerHighVol = maxVolOverflow × pct/100`. |
### Output formats
- **Process Output** — format for Port 0 (`process` / `json` / `csv`).
- **Database Output** — format for Port 1 (`influxdb` / `json` / `csv`).
> **Tip — always configure every field.** The pumpingStation mixes geometry and control thresholds freely. Leaving `heightOverflow` at the schema default of 2.5 m while sizing the basin for 10 m walls produces nonsensical fill-percentages and spurious safety events. See the [EVOLV flow-layout rules §9](https://gitea.wbd-rd.nl/RnD/EVOLV/src/branch/main/.claude/rules/node-red-flow-layout.md) for the completeness rule.
## Input topics
All commands enter on the single input port. `msg.topic` selects the handler; `msg.payload` carries the argument.
### `changemode`
```json
{ "topic": "changemode", "payload": "manual" }
```
Switches the active control strategy. The new mode must be in `config.control.allowedModes` — unknown values are rejected with a warning. Typical transitions: `levelbased ⇄ manual` for operator override during maintenance.
### `calibratePredictedVolume`
```json
{ "topic": "calibratePredictedVolume", "payload": 3.4 }
```
Hard-reset the predicted volume time-series to the supplied value (m³). Also rewrites the predicted level (derived from the constant-area geometry) and resets the internal flow-integrator state. Use this when a trustworthy measured level becomes available.
### `calibratePredictedLevel`
```json
{ "topic": "calibratePredictedLevel", "payload": 1.8 }
```
Same as above, but caller supplies a level (m). The predicted volume is recomputed via `volume = level × surfaceArea`.
### `q_in`
```json
{ "topic": "q_in", "payload": 300, "unit": "l/s" }
```
Inject a **manual inflow** into the basin. Registered as a predicted flow under the synthetic child `manual-qin` at position `in`. Useful when no physical inflow sensor is wired but the inflow is known externally (e.g. fed from a sewer model).
### `Qd`
```json
{ "topic": "Qd", "payload": 75 }
```
Forward a manual demand to every child aggregator (MGC first, then any direct pumps). **Only honoured when `config.control.mode === 'manual'`** — in any other mode the command is logged and discarded. Mirrors how `rotatingMachine` gates commands behind its mode field. The interpretation of the number depends on the child's scaling (`absolute` = m³/h, `normalized` = 0100 %).
### `registerChild`
Internal. Child nodes (measurements, rotatingMachines, machineGroupControls, nested pumpingStations) emit this on their Port 2 a few hundred ms after deploy. The station resolves the Node-RED node id back to the source object and registers it via `childRegistrationUtils`.
## Output ports
### Port 0 — process data
Delta-compressed payload (only changed fields per tick). Keys follow the standard 4-segment format `<type>.<variant>.<position>.<childId>` plus a handful of top-level state fields merged in by `getOutput()`:
| Key | Meaning |
|---|---|
| `volume.predicted.atequipment.default` | Running predicted volume from the flow integrator (m³). |
| `volume.measured.atequipment.default` | Volume derived from a `measured` level sensor (m³). |
| `level.predicted.atequipment.default` | Predicted level = `volume / area` (m). |
| `level.measured.<position>.<childId>` | Raw level sensor reading (m). |
| `volumePercent.predicted.atequipment.default` | `(vol - minVol) / (maxVolOverflow - minVol) × 100` (%). |
| `flow.predicted.in.<childId>` | Inflow contribution from a registered child (m³/s internally; editor unit on output). |
| `flow.predicted.out.<childId>` | Outflow contribution from a registered child. |
| `flow.measured.<position>.<childId>` | Flow sensor reading. |
| `netFlowRate.<variant>.atequipment.default` | Net flow used for control (inflow outflow). |
| `direction` | `filling` / `draining` / `steady` / `unknown`. |
| `flowSource` | Which variant drove the current control cycle (`measured`, `predicted`, `level:predicted`, `null`). |
| `timeleft` | Predicted seconds to overflow (while filling) or to dry-run (while draining). |
| `volEmptyBasin`, `heightInlet`, `heightOverflow`, `maxVol`, `maxVolOverflow`, `minVol`, `minVolIn`, `minVolOut`, `minHeightBasedOn` | Echoes of the basin geometry for dashboards. |
| `percControl` | Last demand (0100+ %) forwarded to the machine group during level-based control. |
Consumers must cache and merge deltas — the example dashboard flows include a reusable function node that does exactly this.
### Port 1 — dbase (InfluxDB)
Line-protocol payload for the `telemetry` bucket. Tags stay low-cardinality (station name, asset type); fields carry the numeric state. See [EVOLV — InfluxDB Schema Design](https://gitea.wbd-rd.nl/RnD/EVOLV/src/branch/main/wiki/concepts/influxdb-schema-design.md).
### Port 2 — parent
`{ topic: "registerChild", payload: <this-node-id>, positionVsParent, distance }` — fired once ~100 ms after deploy so an upstream cascade can discover this station. Nested stations use this to register with an outer `pumpingStation` parent.
## Basin model
The basin is modelled as a rectangular prism with constant cross-section. Everything derives from `volume = level × surfaceArea`.
![Basin model — physical layout with control thresholds](diagrams/basin-model.drawio.svg)
*Editable source: [`diagrams/basin-model.drawio`](diagrams/basin-model.drawio). See [`diagrams/README.md`](diagrams/README.md) for the edit-and-export workflow.*
**Typical ordering** (bottom → top): `stopLevel < heightInlet < startLevel = minFlowLevel < maxFlowLevel ≤ heightOverflow`.
> ⚠️ The comment block in `specificClass.js` currently says `startLevel ≤ heightInlet` (inlet above startLevel). The physical convention is the opposite: pumps start *before* the water reaches the gravity inlet, so `heightInlet < startLevel`. Worth fixing in the code comment next time that file is touched.
**minHeightBasedOn** — which pipe defines `minVol`, the operational floor used for the initial seed, the dry-run trigger, and the 0 % point of the fill percentage:
```
outlet (default): inlet:
● maxVolOverflow ● maxVolOverflow
│ │
● heightInlet ● heightInlet ─── minVol
│ │
● heightOutlet ──── minVol ● heightOutlet
│ │
● floor ● floor
Buffer counts as usable stock. Buffer reserved; 0% fill
starts at the inlet.
```
## Net-flow selection
Every tick, `_selectBestNetFlow()` walks a priority ladder and returns the first net flow that clears the dead-band (`|flow| ≥ flowThreshold`):
```
priority source note
1 ────● measured.flow real sensors on inflow/outflow
2 ────● predicted.flow manual q_in + pump-curve outputs
3 ────● level:measured dL/dt × surfaceArea
4 ────● level:predicted dL/dt of the integrator
5 ────● steady (fallback) warn, return { value: 0, source: null }
```
Both **measured** and **predicted** variants are always computed and stored, regardless of which one drives control. The active source surfaces on Port 0 as `flowSource`, so operators can watch sensor drift (measured diverges from predicted), validate the volume integrator, and diagnose "which source was active when X happened?".
The inflow / outflow alias map is deliberately wide so measurements (`upstream`/`downstream`) and predicted-flow subscriptions (`in`/`out`) both feed the same aggregator:
```js
flowPositions = { inflow: ['in', 'upstream'], outflow: ['out', 'downstream'] }
```
## Control logic
The `pumpingStation` supports multiple control modes. Each mode is a **policy that sets the three control thresholds (`minLevel`, `startLevel`, `maxLevel`) and produces a demand (0 100 %)** — the two safety thresholds (`dryRunLevel`, `overflowLevel`) are mode-independent and handled by the safety layer below.
Every mode gets its own page under [`modes/`](modes/README.md) with a consistent layout (inputs, threshold policy, demand formula, edge cases) so they can be compared side-by-side. Currently:
| Mode | Status | Page |
|---|---|---|
| `levelbased` | ✅ implemented | [modes/levelbased.md](modes/levelbased.md) |
| `manual` | ✅ implemented (via `Qd` topic) | — |
| `flowbased`, `pressureBased`, `percentageBased`, `powerBased`, `hybrid` | 🚧 placeholder in code | — |
See [`modes/README.md`](modes/README.md) for the index and page template.
## Safety controller
`_safetyController` runs **before** `_controlLogic` every tick. Two rules, deliberately asymmetric — *dry-run protects the pumps from running themselves into air*, *overfill protects the basin from spilling*.
![Safety rules — dry-run vs overfill](diagrams/safety-rules.drawio.svg)
During overfill, level-based control naturally commands ≥100 % on the downstream MGC because the level is above `maxFlowLevel`.
> ⚠️ **Known limitation — gravity-sewer context.** The "upstream STOP" action only makes sense in a **cascaded** station layout where the upstream equipment is an EVOLV-controllable pump or station. In a conventional wastewater wet-well the inflow is gravity-fed from the municipal sewer and **cannot be stopped** — attempting to would back up toilets. For that case the correct response to an overfill event is to **measure and log the spill over the weir** (for compliance reporting) and raise an alarm, while keeping downstream pumps at maximum demand. The current code fires `execSequence: shutdown` on upstream children regardless of what they are; that should be gated on "is the upstream actually controllable?" and supplemented with overflow-rate tracking. Tracked as follow-up work.
A missing volume reading is treated as a hard fault: every direct machine is sent `execSequence: shutdown` and `safetyControllerActive` latches. Calibrate predicted volume (`calibratePredictedVolume`) or wire a level measurement to recover.
## Registration — which children count as flow?
`_registerPredictedFlowChild` subscribes only to the *highest-level aggregator* to prevent double-counting.
```
Without MGC: With MGC:
[ PumpingStation ] [ PumpingStation ]
│ │ │ │
│ │ │ [ MGC ]
│ │ │ │ │ │
● ● ● ● ● ●
(each pump subscribed (only MGC is subscribed;
directly) MGC aggregates its pumps)
N flow subscriptions. 1 flow subscription.
Risk: double-count if an Pumps' flow is already
MGC is added later. inside the MGC total.
```
Measurement children register separately via `_registerMeasurementChild` and feed the `measured` variant — they never collide with the predicted-flow subscription. Nested `pumpingStation` children are always subscribed and expose their net flow at the parent's position.
## Node status badge
Updated every second by `_updateNodeStatus` in `nodeClass.js`:
```
⬆️ 42.3% | V=4.57 / 10.80 m³ | net: 180 m³/h | t≈12 min
```
| Symbol | Direction | Badge colour |
|---|---|---|
| ⬆️ | `filling` | blue |
| ⬇️ | `draining` | orange |
| ⏸️ | `steady` | green |
| ❔ | `unknown` / missing measurements | grey |
## Example flow
The canonical end-to-end demo lives in the EVOLV superproject at [`examples/pumpingstation-3pumps-dashboard/`](https://gitea.wbd-rd.nl/RnD/EVOLV/src/branch/main/examples/pumpingstation-3pumps-dashboard). It wires three `rotatingMachine` pumps beneath an MGC beneath a `pumpingStation`, with the dashboard layout rule set (see the [EVOLV flow-layout rules](https://gitea.wbd-rd.nl/RnD/EVOLV/src/branch/main/.claude/rules/node-red-flow-layout.md)) — a useful template for any new station.
## Troubleshooting
| Symptom | Likely cause | Fix |
|---|---|---|
| `fill %` exceeds 100 % or is negative | Basin geometry inconsistent — e.g. `heightOverflow > heightBasin`, or `heightOutlet > heightInlet`. | Cross-check `0 < heightOutlet < heightInlet < heightOverflow ≤ heightBasin` in the editor. |
| Pumps never start in `levelbased` | Level is stuck in the DEAD ZONE between `stopLevel` and `startLevel`, or `minFlowLevel == maxFlowLevel` so scaling collapses. | Widen the control band: move `startLevel` above `stopLevel` and set `maxFlowLevel ≈ heightOverflow`. |
| "No volume data available to safe guard system; shutting down all machines." in logs | No measured level, predicted volume not calibrated, and no inflow/outflow samples yet. | Issue `calibratePredictedVolume` (or `calibratePredictedLevel`) once at startup, or wire a level sensor. |
| `flowSource: null` and `direction: 'steady'` forever | Every flow / level signal falls inside the dead-band (default `1e-4 m³/s`). | Confirm flows are non-zero, or lower `config.general.flowThreshold` for a small-scale demo. |
| `Qd` ignored | Station is not in `manual` mode. | Send `{ topic: 'changemode', payload: 'manual' }` first, or fall back to level-based control. |
| Pumps keep running during overfill | Intended — overfill safety only stops **upstream** equipment; downstream pumps must drain. | To override, switch to `manual` and set `Qd = 0`, or issue an emergency-stop at the MGC. |
| Predicted volume drifts away from measured | Flow integrator has no reference — flows might have the wrong sign, or `unit` is mis-declared. | Call `calibratePredictedVolume` periodically from a measured level. |
## Running it locally
```bash
git clone --recurse-submodules https://gitea.wbd-rd.nl/RnD/EVOLV.git
cd EVOLV
docker compose up -d
# Node-RED: http://localhost:1880 InfluxDB: :8086 Grafana: :3000
```
Then in Node-RED: **Import ▸ Examples ▸ EVOLV ▸ pumpingStation** (or open `examples/pumpingstation-3pumps-dashboard/flow.json`).
## Testing
```bash
cd nodes/pumpingStation
npm test
```
Unit tests live in `test/specificClass.test.js` — construction, basin derivation, measurement registration, net-flow selection, safety interlocks, and calibration.
## Related
- [rotatingMachine wiki](https://gitea.wbd-rd.nl/RnD/rotatingMachine/wiki) — atomic pump model beneath pumpingStation / MGC.
- [measurement wiki](https://gitea.wbd-rd.nl/RnD/measurement/wiki) — sensor conditioning for inflow, outflow, level, and pressure inputs.
- [machineGroupControl wiki](https://gitea.wbd-rd.nl/RnD/machineGroupControl/wiki) — how MGC coordinates multiple pumps.
- [EVOLV — Node Architecture](https://gitea.wbd-rd.nl/RnD/EVOLV/src/branch/main/wiki/architecture/node-architecture.md) — the entry → nodeClass → specificClass pattern.
- [EVOLV — Group Optimization](https://gitea.wbd-rd.nl/RnD/EVOLV/src/branch/main/wiki/architecture/group-optimization.md) — pump-group scheduling theory.
- [EVOLV — flow-layout rules](https://gitea.wbd-rd.nl/RnD/EVOLV/src/branch/main/.claude/rules/node-red-flow-layout.md) — the lane / group / channel layout rules used by the demo flows.