Aligns the code with the 5-threshold convention used throughout the
wiki (basin model + per-mode transfer-function diagrams):
heightInlet → inflowLevel
heightOutlet → outflowLevel
heightOverflow → overflowLevel
stopLevel → minLevel
maxFlowLevel → maxLevel
minFlowLevel → removed (collapsed into startLevel; they were
always supposed to hold the same value)
minVolIn → minVolAtInflow
minVolOut → minVolAtOutflow
maxVolOverflow → maxVolAtOverflow
startLevel → unchanged
Config schema (generalFunctions/src/configs/pumpingStation.json) is
updated in a parallel commit in that submodule.
Also:
- Stripped the ~150-line ASCII basin diagram from initBasinProperties
JSDoc; it now points at wiki/functional-description.md#basin-model.
- Trimmed the top-of-class JSDoc — the config-sections breakdown was
drifting from the schema anyway; wiki is now the source of truth.
- Tidied inline comments in _controlLevelBased, _scaleLevelToFlowPercent.
- Editor order reshuffled to match the bottom→top basin order:
minLevel, startLevel, maxLevel.
Breaking change for saved flows: existing pumpingStation nodes in
production flows reference the old field names and will need to be
re-entered in the editor. No compat shim — node is RnD/trial.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
Two additions to pumpingStation:
1. _controlLevelBased now calls _applyMachineGroupLevelControl in
addition to _applyMachineLevelControl when the basin is filling
above startLevel. Previously only direct-child machines received
the level-based percent-control signal; in a hierarchical topology
(PS → MGC → pumps) the machines sit under MGC and PS.machines is
empty, so the level control never reached them.
2. New 'Qd' input topic + forwardDemandToChildren() method. When PS
is in 'manual' mode (matching the pattern from rotatingMachine's
virtualControl), operator demand from a dashboard slider is forwarded
to all child machine groups and direct machines. When PS is in any
other mode (levelbased, flowbased, etc.), the Qd msg is silently
dropped with a debug log so the automatic control isn't overridden.
No breaking changes — existing flows that don't send 'Qd' are unaffected,
and _controlLevelBased's additional call to machineGroupLevelControl
is a no-op when no machine groups are registered.
Co-Authored-By: Claude Opus 4.6 (1M context) <noreply@anthropic.com>
Replaces manual base config construction with shared buildConfig() method.
Node now only specifies domain-specific config sections.
Part of #1: Extract base config schema
Co-Authored-By: Claude Opus 4.6 <noreply@anthropic.com>