Commit Graph

4 Commits

Author SHA1 Message Date
znetsixe
2e4ad8d3f1 fix(levelBased): drop hold zone, route through MGC.setDemand, add holdLevel + integrator variant pick; slim npm pack
levelBased ramp + engagement:
- Ramp foot is now max(startLevel, holdLevel) — was max(startLevel,
  inflowLevel). inflowLevel is basin geometry, not a control setpoint;
  the implicit hold zone it created was causing pumps to "start at
  inflowLevel" instead of startLevel.
- New optional `holdLevel` config (defaults to startLevel = no hold band).
  When raised, pumps engage at startLevel and hold at 0 % = MGC flow.min
  across [startLevel, holdLevel], then ramp 0..100 % to maxLevel.
- Engagement decided in run() (not in `_applyMachineGroupLevelControl`):
  rising-edge hysteresis arming gates a clean turnOff early-return.
  Once armed, the helper always forwards setDemand(pct, '%') — 0 %
  legitimately means "engaged at min flow", no more soft-turnOff at
  the boundary.
- Disengagement paths (minLevel hard-stop, stopLevel falling-edge,
  pre-arming idle) now all clear the shifted-ramp hysteresis state too.
- Threshold validator drops the startLevel ≤ inflowLevel rule; adds
  startLevel ≤ holdLevel < maxLevel (only checked when holdLevel is
  explicitly set, so default-null doesn't false-flag).

MGC unit math:
- Replace direct group.handleInput(percent) with group.setDemand(pct, '%')
  in _applyMachineGroupLevelControl. The percent → m³/s resolution now
  lives in MGC.setDemand (committed separately in the MGC submodule).

FlowAggregator variant picking:
- New _pickFlowSum() helper mirrors selectBestNetFlow's variant
  precedence (measured first, then predicted) and resolves each side
  independently. Realistic mixed case — real measured upstream sensor +
  predicted pump outflow — now feeds the predicted-volume integrator.
  Was reading only `flow.predicted.*` so a real upstream sensor
  (which writes `flow.measured.*`) never moved the level.

Editor:
- New `holdLevel` and `deadZoneKeepAlivePercent` defaults + side-panel
  input rows in the levelbased mode preview.
- Add the missing `ps-mode-line-holdLevel` SVG marker (was declared in
  the side-panel coupling but the SVG element didn't exist, so the
  dashed line never rendered).
- Relax stopLevel marker gate so it renders for any non-negative typed
  value — start/stop ordering is the ribbon's job, not the marker's
  (was hiding the line whenever startLevel was momentarily smaller).
- Add holdLevel to the marker loop in mode-preview so changes track.
- Add stopLevel + holdLevel + maxLevel to all three bindRedraw lists
  (basin-diagram, mode-preview, bounds.apply) so the SVG, validation
  ribbon, and HTML5 min/max attrs update on every edit.
- Initialise stopLevel + holdLevel + deadZoneKeepAlivePercent inputs
  in oneditprepare so reopening the editor shows the saved values.
- nodeClass passes holdLevel + deadZoneKeepAlivePercent into the
  domain config.

Tests:
- New test/basic/_probe_upstream_emit.test.js: confirms the parent
  surfaces flow.measured.upstream.* on Port 0 after a measurement
  child write — pins the previously-invisible measured variant flow.
- flowAggregator.basic.test.js: two new regression cases — measured
  inflow when predicted side is empty, and the measured-in /
  predicted-out mixed case.
- control-levelBased.basic.test.js: new cases for the holdLevel hold
  band, the [stopLevel, startLevel] keep-alive, the engagement gate,
  and the "0 % at startLevel = setDemand" contract.
- specificClass.test.js: zone tests adjusted to the new ramp foot.
  Shifted-ramp tests pin holdLevel = 3 explicitly so their legacy
  arithmetic (ramp foot at inflowLevel) stays self-consistent.
- shifted-ramp-end-to-end.test.js: same holdLevel pin for the same
  reason.

Packaging:
- Add .gitignore + .npmignore so the published tarball drops the
  wiki/, simulations/, test/, tools/, .claude/ etc. The pack went
  from 1.5 MB (72 files) to ~57 KB (30 files).

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-05-19 21:36:29 +02:00
Rene De Ren
62bc73f2f9 Editor: dynamic input bounds + full hierarchy validation, layout polish
Bounds (new src/editor/bounds.js):
- Sets HTML5 min/max on every level + percent input each redraw,
  derived from the current values of related inputs so the spinner
  stops at the basin hierarchy:
  0 < outflowLevel < dryRunLevel < startLevel ≤ inflowLevel
      ≤ shiftLevel ≤ maxLevel ≤ overflowLevel ≤ basinHeight
- dryRunPercent capped so dryRunLevel ≤ startLevel given current outflow.
- shiftArmPercent ∈ [1, 100]; highVolumeSafety% ∈ [1, 100].

Validation:
- New visible ribbon above the basin diagram (#ps-basin-validation)
  listing every hierarchy violation. The in-SVG warning text is now a
  small reminder ("⚠ N ordering issues").
- basin-diagram.js owns hierarchy issues; mode-preview.js trimmed to
  only own shift-specific issues (shift > start, shift ≤ max,
  shiftArmPercent range, shiftLevel required-when-enabled).
- oneditsave blocks Deploy on the union of _psBasinValidationIssues
  and _psModeValidationIssues with a RED.notify listing all problems.

Layout polish:
- Side panel widened to 220 px with minmax(0, 1fr) first column so long
  labels can no longer push the rows past the panel edge.
- Basin SVG max-width 380 → 360, gap between side panel and SVG bumped
  14 → 28 px. Tank shifted right (x=145 width=110) so the inlet
  "bottom of pipe" sub-label is no longer clipped on the left edge.
- "0 m (datum)" moved below the tank (y=395, centred) so it can't
  collide with "Outlet / top of pipe" when outflowLevel is near floor.
- Zone labels shortened (Spare / Sewage + buffer / Buffer / Dead vol)
  and only show when the bracketing thresholds are ≥ 28 px apart, so
  they never sit on a threshold label.
- Mode preview axis labels under the chart removed — line colour +
  side-panel labels + hover-couple already identify each line. Stub
  <text> elements left hidden to keep the redraw loop simple. Arm-%
  line + label trimmed in 10 px on the right so they're not clipped.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-05-06 14:10:22 +02:00
Rene De Ren
de9a79b888 Hold-then-ramp shift semantics + shiftArmPercent + e2e tests
Runtime (specificClass.js):
- Replace the "shift left both ramp ends" geometry with a true
  hold-then-ramp hysteresis driven by output %, not level:
  • Up-curve % crosses shiftArmPercent on the way up → ARM.
  • Filling→draining transition while armed → capture the up-curve %
    at that moment as _shiftHoldValue.
  • Draining + level ≥ shiftLevel → output stays at _shiftHoldValue
    (horizontal hold, matching the dashed segment in the SVG).
  • Draining + level in [start, shift] → output ramps holdValue → 0 %
    along the same curve shape (linear or log) as the up curve.
  • Draining + level < startLevel → 0 % AND disarm.
  • Returning to filling clears holdValue, stays armed; next drain
    transition captures a fresh hold so bouncing fills rearm cleanly.
  • Disarm only when level ≤ startLevel.
- New _curveShape(x) helper for shared linear/log shaping.
- Removed legacy _levelBasedRampStart / _levelBasedRampTop /
  _updateShiftArmed in favour of the inline state machine.

Adapter (nodeClass.js):
- Pipe shiftArmPercent through to control.levelbased.

Editor (pumpingStation.html + src/editor/):
- Add shiftArmPercent input row (% with unit) to the mode side panel
  (only shown when shifted ramp is enabled). Default 95 %.
- Add the horizontal arming-% line + label inside the mode SVG —
  this is the "% Threshold triggering shifted ramp down" line from
  the original drawing that had been missing.
- Redraw the shifted-down curve to match the SVG geometry literally:
  100 % flat from maxLevel → shiftLevel, then ramp shiftLevel →
  startLevel down to 0 %, OFF below startLevel. Preview shows the
  worst-case envelope (hold = 100 %); runtime hold is captured live.
- Validation extended: 0 < shiftArmPercent ≤ 100; ordering rules
  preserved (start < shift ≤ max etc.).
- Auto-default shiftArmPercent to 95 when shift is enabled and the
  current value is missing or out of range.

Dashboard example (examples/basic-dashboard.flow.json):
- Parser now reads `level.predicted.atequipment.default` etc. The
  MeasurementContainer flatten format includes the implicit 'default'
  childId; consumers must include it. Comment in the parser points
  at the documenting source in generalFunctions.

Tests:
- test/basic: replace old level-armed-shift tests with two new ones
  that exercise the hold-then-ramp arming, capture, hold, ramp-down,
  disarm, and the bounce case (filling→draining→filling→draining
  captures a fresh hold each time).
- test/integration/shifted-ramp-end-to-end.test.js: new file. Drives
  Q_IN/Q_OUT through the full runtime tick with a controllable clock,
  asserting the same hysteresis path the dashboard exercises.
- test/integration/basic-dashboard-flow.test.js: fixture keys updated
  to the .default-suffixed form so they match the real flatten output.
56/56 tests pass.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-05-06 11:46:46 +02:00
Rene De Ren
8a6ca1baeb Level-armed shift, derived dryRunLevel, side-panel editor + manual q_out
Runtime (specificClass.js):
- Replace direction-based hysteresis with level-armed _shiftArmed state.
  Arms when level rises past shiftLevel; disarms when level drops below
  startLevel. While armed, ramp foot moves to startLevel and ramp top
  to shiftLevel — both ends shift left, then saturate at 100 % up to
  maxLevel.
- _scaleLevelToFlowPercent now takes (rampStartLevel, rampTopLevel) so
  the saturation point follows the shift state.
- New setManualOutflow mirroring setManualInflow.

Adapter (nodeClass.js):
- Pipe enableShiftedRamp / shiftLevel through to control.levelbased.
- New q_out topic handler.

Editor (pumpingStation.html + new src/editor/ modules):
- Split monolithic <script> into modules: index.js (helpers),
  basin-diagram.js, mode-preview.js, hover-couple.js, oneditprepare.js,
  oneditsave.js — served via /pumpingStation/editor/:file.
- Mode preview redrawn per the SVG diagrams: OFF tier below 0 %, 0 %
  flat from start→inlet, ramp inlet→max, optional shifted-down curve
  start→shift with 100 % saturation past shift.
- Mode preview gains zone bands (dryRun / safetyLow / safe / safetyHigh /
  overflow), level markers (dryRun derived, start, inlet, max, shift,
  overflow), validation ribbon that blocks save on bad ordering.
- Auto-default shiftLevel to 0.9 × maxLevel on enable so the marker is
  always visible.
- All level inputs moved to a side panel left of each diagram, color-
  coded to match line strokes; hover-couple highlights the paired SVG
  line on input focus / mouseover.
- Removed UI for non-static parameters: minHeightBasedOn,
  pipelineLength, maxDischargeHead, staticHead, defaultFluid,
  maxInflowRate, temperatureReferenceDegC,
  timeleftToFullOrEmptyThresholdSeconds, inletPipeDiameter,
  outletPipeDiameter, minLevel (now derived = dryRunLevel).
- foreignObject inputs in basin SVG removed (single source of truth in
  side panel).

Dashboard example (examples/basic-dashboard.flow.json):
- Add manual Q_OUT slider + q_out builder mirroring the existing q_in
  trio so the basin can be exercised end-to-end without a connected
  rotating-machine downstream.

Tests (test/basic/specificClass.test.js):
- Replace direction-shift test with two new cases covering shift-disabled
  hold-zone behaviour and shift-armed/disarmed transitions through
  shiftLevel and startLevel boundaries. 53/53 tests pass.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-05-05 19:29:34 +02:00