feat(commands): unit shorthand + collapse duplicated value/unit parsing; wiki sync
- 5 descriptors -> unit: shorthand (cmd.calibrate.volume/level, set.inflow/ outflow/demand). - setInflow/setOutflow: drop the hand-rolled scalar-vs-object parsing — the registry now normalises every shape to a number in the descriptor unit; the handlers become guarded one-liners (matching setDemand). - Regenerate wiki topic-contract + command-envelope note (msg.origin). 143/143 tests green. Co-Authored-By: Claude Opus 4.8 (1M context) <noreply@anthropic.com>
This commit is contained in:
@@ -11,7 +11,11 @@
|
||||
|
||||
## Topic contract
|
||||
|
||||
The **Unit** column reflects each descriptor's `units: { measure, default }` declaration. The default unit is what the commandRegistry coerces incoming `msg.unit` values to before the handler runs.
|
||||
The **Unit** column reflects each descriptor's declared unit (via the `unit: 'm3/h'` shorthand or the legacy `units: { measure, default }`; the measure is derived from the unit). The default unit is what the commandRegistry coerces incoming values to before the handler runs.
|
||||
|
||||
**Command envelope (all EVOLV nodes).** Every command shares one envelope on top of `msg.topic`:
|
||||
- **Value + unit** — send `msg.payload` as a number (with optional sibling `msg.unit`) **or** as `{ value, unit }`. The registry always converts the value to the descriptor's unit before the handler; numeric strings are converted too. A missing unit assumes the descriptor default.
|
||||
- **`msg.origin`** — the control authority that issued the command: `parent` (automation/parent controller, the default), `GUI` (SCADA/HMI operator), or `fysical` (physical buttons). On nodes with a control mode, the mode's `allowedSources` decides which origins are accepted; releasing control is done by changing the mode.
|
||||
|
||||
<!-- BEGIN AUTOGEN: topic-contract -->
|
||||
|
||||
@@ -19,11 +23,11 @@ The **Unit** column reflects each descriptor's `units: { measure, default }` dec
|
||||
|---|---|---|---|---|
|
||||
| `set.mode` | `changemode` | `string` | — | Switch the station between auto / manual control modes. |
|
||||
| `child.register` | `registerChild` | `string` | — | Register a child node (machine group, measurement, …) with this station. |
|
||||
| `cmd.calibrate.volume` | `calibratePredictedVolume` | `any` | `volume` (default `m3`) | Calibrate the predicted-volume integrator to a known basin volume. |
|
||||
| `cmd.calibrate.level` | `calibratePredictedLevel` | `any` | `length` (default `m`) | Calibrate the predicted-volume integrator to a known basin level. |
|
||||
| `set.inflow` | `q_in` | `any` | `volumeFlowRate` (default `m3/h`) | Push a measured inflow value into the basin balance. |
|
||||
| `set.outflow` | `q_out` | `any` | `volumeFlowRate` (default `m3/h`) | Push a measured outflow value into the basin balance. |
|
||||
| `set.demand` | `Qd` | `any` | `volumeFlowRate` (default `m3/h`) | Operator outflow demand setpoint for the station. |
|
||||
| `cmd.calibrate.volume` | `calibratePredictedVolume` | any | `volume` (default `m3`) | Calibrate the predicted-volume integrator to a known basin volume. |
|
||||
| `cmd.calibrate.level` | `calibratePredictedLevel` | any | `length` (default `m`) | Calibrate the predicted-volume integrator to a known basin level. |
|
||||
| `set.inflow` | `q_in` | any | `volumeFlowRate` (default `m3/h`) | Push a measured inflow value into the basin balance. |
|
||||
| `set.outflow` | `q_out` | any | `volumeFlowRate` (default `m3/h`) | Push a measured outflow value into the basin balance. |
|
||||
| `set.demand` | `Qd` | any | `volumeFlowRate` (default `m3/h`) | Operator outflow demand setpoint for the station. |
|
||||
|
||||
<!-- END AUTOGEN: topic-contract -->
|
||||
|
||||
|
||||