stopLevel Schmitt-trigger hysteresis + dead-zone keep-alive
Levelbased control now distinguishes startLevel (rising-edge engage, ramp foot) from stopLevel (falling-edge disengage). _stopHystRunning flag flips TRUE crossing startLevel up, FALSE crossing stopLevel down. While engaged AND level inside [stopLevel, startLevel] (basin draining through the dead band), emit a configurable keep-alive percControl (default 1 %) so MGC keeps a single pump running for a full drain stroke instead of oscillating at startLevel. Hard turn-off the moment level <= stopLevel — independent of ramp scaling. Manual-mode demand=0 now also issues explicit turnOff to keep parity with the new MGC handleInput semantics where demand<=0 means "off". Editor preview shades the new hysteresis band; admin endpoint exposes runtime engaged state. Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
This commit is contained in:
@@ -66,6 +66,7 @@ class nodeClass {
|
||||
levelbased:{
|
||||
minLevel:uiConfig.minLevel,
|
||||
startLevel:uiConfig.startLevel,
|
||||
stopLevel: uiConfig.stopLevel,
|
||||
maxLevel:uiConfig.maxLevel,
|
||||
curveType: uiConfig.levelCurveType || uiConfig.curveType,
|
||||
logCurveFactor: uiConfig.logCurveFactor,
|
||||
|
||||