Docs + simulations refresh; align spill-flow keys with new position
- wiki/functional-description.md: rename Overfill Protection → High-volume
Safety; tighten basin-ordering chain; relocate level-based mode
diagrams under wiki/diagrams/modes/level-based/; document the new
flow.predicted.overflow.default position (replaces the previous
child='overflow' under position 'out'); add underflowVolume +
predictedUnderflowVolume entries.
- wiki/modes/{levelbased,powerbased}.md: paragraph cleanups.
- wiki/diagrams: move level-linear basin diagram under modes/level-based/
alongside a new level-log variant.
- simulations/run.js: add max_demand_gt expectation.
- simulations/scenarios/*: minor fixture updates.
- test/basic/nodeClass-config.test.js: new config-shape coverage.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
This commit is contained in:
@@ -1,31 +1,31 @@
|
||||
// Storm surge — inflow triples briefly, pumps should saturate at 100%,
|
||||
// level rises toward overflow then recedes.
|
||||
// Storm surge — inflow triples briefly, pumps should increase demand as
|
||||
// the level enters the rising ramp.
|
||||
//
|
||||
// Expectation: during the surge (t=300..600), demand reaches 100% and
|
||||
// level may transiently climb above maxLevel. Overflow safety should
|
||||
// fire if the surge overwhelms pump capacity; dry-run should not fire.
|
||||
// Expectation: during the surge (t=300..600), demand rises but remains
|
||||
// bounded. High-volume safety should fire if the surge overwhelms pump
|
||||
// capacity; dry-run should not fire.
|
||||
|
||||
module.exports = {
|
||||
name: 'levelbased-storm',
|
||||
description: 'Sewer inflow triples from 0.008 → 0.024 m³/s for 5 minutes then returns to baseline. Overfill safety may engage.',
|
||||
description: 'Sewer inflow triples from 0.008 → 0.024 m³/s for 5 minutes then returns to baseline. High-volume safety may engage.',
|
||||
durationSec: 1500,
|
||||
|
||||
config: {
|
||||
general: { name: 'EvalStorm', id: 'eval-storm', unit: 'm3/h',
|
||||
logging: { enabled: false, logLevel: 'error' } },
|
||||
functionality: { softwareType: 'pumpingStation', role: 'stationcontroller', positionVsParent: 'atEquipment' },
|
||||
basin: { volume: 50, height: 5, inflowLevel: 3, outflowLevel: 0.2, overflowLevel: 4.5 },
|
||||
basin: { volume: 50, height: 5, inflowLevel: 3, outflowLevel: 0.2, overflowLevel: 4.5, inletPipeDiameter: 0.4, outletPipeDiameter: 0.3 },
|
||||
hydraulics: { refHeight: 'NAP', basinBottomRef: 0, minHeightBasedOn: 'outlet' },
|
||||
control: {
|
||||
mode: 'levelbased',
|
||||
allowedModes: new Set(['levelbased']),
|
||||
levelbased: { minLevel: 1, startLevel: 2, maxLevel: 4 },
|
||||
levelbased: { minLevel: 1, startLevel: 2, maxLevel: 4, curveType: 'linear', logCurveFactor: 9 },
|
||||
},
|
||||
safety: {
|
||||
enableDryRunProtection: true,
|
||||
dryRunThresholdPercent: 2,
|
||||
enableOverfillProtection: true,
|
||||
overfillThresholdPercent: 95,
|
||||
enableHighVolumeSafety: true,
|
||||
highVolumeSafetyThresholdPercent: 95,
|
||||
timeleftToFullOrEmptyThresholdSeconds: 0,
|
||||
},
|
||||
},
|
||||
@@ -55,6 +55,6 @@ module.exports = {
|
||||
{ name: 'dry-run never trips', type: 'end_state_eq', field: 'safetyActive', value: false },
|
||||
// Level may exceed maxLevel transiently but must stay under basinHeight
|
||||
{ name: 'level never breaches physical basin', type: 'max_level_bounded', value: 5.0 },
|
||||
{ name: 'demand saturates at 100% during surge', type: 'max_demand_bounded', value: 100 },
|
||||
{ name: 'demand remains bounded during surge', type: 'max_demand_bounded', value: 100 },
|
||||
],
|
||||
};
|
||||
|
||||
Reference in New Issue