Docs + simulations refresh; align spill-flow keys with new position
- wiki/functional-description.md: rename Overfill Protection → High-volume
Safety; tighten basin-ordering chain; relocate level-based mode
diagrams under wiki/diagrams/modes/level-based/; document the new
flow.predicted.overflow.default position (replaces the previous
child='overflow' under position 'out'); add underflowVolume +
predictedUnderflowVolume entries.
- wiki/modes/{levelbased,powerbased}.md: paragraph cleanups.
- wiki/diagrams: move level-linear basin diagram under modes/level-based/
alongside a new level-log variant.
- simulations/run.js: add max_demand_gt expectation.
- simulations/scenarios/*: minor fixture updates.
- test/basic/nodeClass-config.test.js: new config-shape coverage.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
This commit is contained in:
@@ -2,30 +2,30 @@
|
||||
//
|
||||
// Expectation: with a stable inflow of 0.008 m³/s and a pump bank with
|
||||
// max capacity 0.012 m³/s, the level settles in the RAMP zone (between
|
||||
// startLevel and maxLevel) at roughly the point where demand matches
|
||||
// inflowLevel and maxLevel while filling) at roughly the point where demand matches
|
||||
// inflow. No safety trips should fire.
|
||||
|
||||
module.exports = {
|
||||
name: 'levelbased-steady',
|
||||
description: 'Constant sewer inflow below pump capacity; level converges inside the RAMP zone with demand matching inflow.',
|
||||
durationSec: 1200,
|
||||
durationSec: 3600,
|
||||
|
||||
config: {
|
||||
general: { name: 'EvalSteady', id: 'eval-steady', unit: 'm3/h',
|
||||
logging: { enabled: false, logLevel: 'error' } },
|
||||
functionality: { softwareType: 'pumpingStation', role: 'stationcontroller', positionVsParent: 'atEquipment' },
|
||||
basin: { volume: 50, height: 5, inflowLevel: 3, outflowLevel: 0.2, overflowLevel: 4.5 },
|
||||
basin: { volume: 50, height: 5, inflowLevel: 3, outflowLevel: 0.2, overflowLevel: 4.5, inletPipeDiameter: 0.4, outletPipeDiameter: 0.3 },
|
||||
hydraulics: { refHeight: 'NAP', basinBottomRef: 0, minHeightBasedOn: 'outlet' },
|
||||
control: {
|
||||
mode: 'levelbased',
|
||||
allowedModes: new Set(['levelbased']),
|
||||
levelbased: { minLevel: 1, startLevel: 2, maxLevel: 4 },
|
||||
levelbased: { minLevel: 1, startLevel: 2, maxLevel: 4, curveType: 'linear', logCurveFactor: 9 },
|
||||
},
|
||||
safety: {
|
||||
enableDryRunProtection: true,
|
||||
dryRunThresholdPercent: 2,
|
||||
enableOverfillProtection: true,
|
||||
overfillThresholdPercent: 98,
|
||||
enableHighVolumeSafety: true,
|
||||
highVolumeSafetyThresholdPercent: 98,
|
||||
timeleftToFullOrEmptyThresholdSeconds: 0,
|
||||
},
|
||||
},
|
||||
@@ -44,7 +44,7 @@ module.exports = {
|
||||
ps.measurements.type('flow').variant('predicted').position('out').child('mgc1').value(outflow, Date.now(), 'm3/s');
|
||||
},
|
||||
};
|
||||
ps.calibratePredictedLevel(2.0); // start at the bottom of the RAMP zone
|
||||
ps.calibratePredictedLevel(2.0); // start at the mode start level, below the rising ramp
|
||||
},
|
||||
|
||||
inputs: (t, ps) => {
|
||||
@@ -55,6 +55,7 @@ module.exports = {
|
||||
{ name: 'no safety trips', type: 'safety_trips_eq', value: 0 },
|
||||
{ name: 'level stays below overflow', type: 'max_level_bounded', value: 4.5 },
|
||||
{ name: 'level stays above outflow', type: 'min_level_bounded', value: 0.2 },
|
||||
{ name: 'rising ramp engages after inlet level', type: 'max_demand_gt', value: 0 },
|
||||
{ name: 'no threshold issues on init', type: 'threshold_issues_eq', value: 0 },
|
||||
],
|
||||
};
|
||||
|
||||
Reference in New Issue