docs(contract): close output-contract gaps — mode/manualDemand, Port-2 topic, output manifest
- wiki/Reference-Contracts.md: regenerate data-model (npm run wiki:all) so the two live getOutput() keys `mode` and `manualDemand` are documented; refresh stale sample values; bump code-ref badge -> a83a85e; add human note describing the two control-state keys. - CONTRACT.md: fix Port-2 outgoing topic registerChild -> child.register (registerChild is the deprecated *input* alias, not what the node emits). - test/_output-manifest.md: add the mandatory output manifest (Port 0/1/2 + emitter events + the 15-way fn_status_split fan-out) with honest coverage gaps. - test/integration/basic-dashboard-flow.test.js: fix stale fan-out count 14->15 (output 14 = percControl chart added upstream); assert out[14]. Co-Authored-By: Claude Opus 4.8 (1M context) <noreply@anthropic.com>
This commit is contained in:
@@ -25,8 +25,9 @@ Aliases log a one-time deprecation warning the first time they fire.
|
||||
- **Port 1 (InfluxDB telemetry):** same shape as Port 0, formatted with the
|
||||
`'influxdb'` formatter.
|
||||
- **Port 2 (registration):** at startup the node sends one
|
||||
`{ topic: 'registerChild', payload: <node.id>, positionVsParent, distance }`
|
||||
to the upstream parent.
|
||||
`{ topic: 'child.register', payload: <node.id>, positionVsParent, distance }`
|
||||
to the upstream parent (`child.register` is canonical; `registerChild` is the
|
||||
deprecated *input* alias, not what this node emits).
|
||||
|
||||
## Events emitted by `source.measurements.emitter`
|
||||
|
||||
|
||||
101
test/_output-manifest.md
Normal file
101
test/_output-manifest.md
Normal file
@@ -0,0 +1,101 @@
|
||||
# pumpingStation output manifest
|
||||
|
||||
> Single source of truth for **what this node emits and where it is tested**, per
|
||||
> [`.claude/rules/output-coverage.md`](https://gitea.wbd-rd.nl/RnD/EVOLV/src/branch/development/.claude/rules/output-coverage.md).
|
||||
> Generated against code-ref `a83a85e`. Regenerate the wiki contract with
|
||||
> `npm run wiki:all` and re-check this table whenever `getOutput()`,
|
||||
> `src/commands/index.js`, or an `examples/*.json` fan-out changes.
|
||||
|
||||
**Null convention for this node:** a Port-0 key whose source is not yet
|
||||
available is emitted as **explicit `null`** (e.g. `timeleft`, `flowSource`,
|
||||
`manualDemand` outside manual mode), never silently absent. Delta-compression on
|
||||
Port 0 then drops keys whose value is unchanged since the previous tick.
|
||||
|
||||
## Port 0 (process data) — `specificClass.getOutput()` → `outputUtils.formatMsg(..., 'process')`
|
||||
|
||||
`msg.topic = config.general.name`. Keys below are the full pre-delta-compression set.
|
||||
|
||||
| Key | Source | Type | States tested | Test file |
|
||||
|---|---|---|---|---|
|
||||
| `mode` | `getOutput` ← `this.mode` | string (`levelbased`/`manual`/`flowbased`/`none`) | populated (`manual`) | test/basic/specificClass.test.js |
|
||||
| `manualDemand` | `getOutput` ← `_manualDemand` | number m³/h, `null` outside manual | populated, null | test/basic/specificClass.test.js |
|
||||
| `direction` | `getOutput` ← `state.direction` | string (`filling`/`draining`/`steady`) | present | test/basic/specificClass.test.js |
|
||||
| `flowSource` | `getOutput` ← `state.flowSource` | string, `null` when no source | null (pre-child) | test/basic/specificClass.test.js |
|
||||
| `timeleft` | `getOutput` ← `state.seconds` | number s, `null` when steady | present, null | test/basic/specificClass.test.js |
|
||||
| `percControl` | `getOutput` ← `controlState.percControl` | number % 0..100 | 0, 25, 50, 75, 85, 100 | test/basic/specificClass.test.js |
|
||||
| `dryRunLevel` | `_computeSafetyPoints` | number m | populated | test/basic/specificClass.test.js |
|
||||
| `dryRunSafetyVol` | `_computeSafetyPoints` | number m³ | populated | test/basic/specificClass.test.js |
|
||||
| `highVolumeSafetyLevel` | `_computeSafetyPoints` | number m | populated | test/basic/specificClass.test.js |
|
||||
| `highVolumeSafetyVol` | `_computeSafetyPoints` | number m³ | populated | test/basic/specificClass.test.js |
|
||||
| `predictedOverflowVolume` | `measurements` overflowVolume | number m³ | populated, 0 | test/basic/specificClass.test.js |
|
||||
| `predictedOverflowRate` | `measurements` flow.overflow | number m³/s | populated, 0 | test/basic/specificClass.test.js |
|
||||
| `predictedUnderflowVolume` | `measurements` underflowVolume | number m³ | 0 | test/basic/specificClass.test.js |
|
||||
| `volume.predicted.atequipment.<childId>` | `measurements.getFlattenedOutput` | number m³ | populated | test/basic/specificClass.test.js |
|
||||
| basin geometry: `heightBasin`, `surfaceArea`, `maxVol`, `minVol`, `maxVolAtOverflow`, `minVolAtInflow`, `minVolAtOutflow`, `volEmptyBasin`, `inflowLevel`, `outflowLevel`, `overflowLevel`, `inletPipeDiameter`, `outletPipeDiameter`, `minHeightBasedOn` | `basin.snapshot()` | number (m/m²/m³) / string | populated | test/basic/specificClass.test.js, test/basic/BasinGeometry.basic.test.js |
|
||||
|
||||
## Port 1 (InfluxDB telemetry) — `formatMsg(..., 'influxdb')`
|
||||
|
||||
Same key set as Port 0 (formatted via the `influxdb` formatter rather than
|
||||
`process`). Field names == Port-0 keys; `config.general.name` is the measurement
|
||||
tag. No Port-1-only fields. Covered transitively by the Port-0 tests above; a
|
||||
dedicated Port-1 line-protocol assertion is a **gap** (see below).
|
||||
|
||||
## Port 2 (registration / control plumbing) — `BaseNodeAdapter._scheduleRegistration`
|
||||
|
||||
| Topic | Source | Payload shape | States tested | Test file |
|
||||
|---|---|---|---|---|
|
||||
| `child.register` | `BaseNodeAdapter.js:122` | `{ topic:'child.register', payload:<node.id>, positionVsParent, distance }` | — | _(gap — see below)_ |
|
||||
|
||||
> Note: the canonical outgoing topic is **`child.register`** (matching the input
|
||||
> registry). Earlier docs said `registerChild`; that is the deprecated input
|
||||
> alias, not what this node emits.
|
||||
|
||||
## Child-facing events — `measurements.emitter`
|
||||
|
||||
Fired as `<type>.<variant>.<position>` when a series receives a value. Parents
|
||||
subscribe by event name (data-driven, not a fixed catalogue):
|
||||
|
||||
| Event | When | Test file |
|
||||
|---|---|---|
|
||||
| `volume.predicted.atequipment` | each integrator tick | test/basic/flowAggregator.basic.test.js |
|
||||
| `level.predicted.atequipment` | recomputed from volume | test/basic/specificClass.test.js |
|
||||
| `flow.predicted.in` (child `manual-qin`) | `set.inflow` handler | test/basic/measurementRouter.basic.test.js |
|
||||
| `overflowVolume`/`underflowVolume`/`flow.predicted.overflow` | integrator hits a physical bound | test/basic/flowAggregator.basic.test.js |
|
||||
|
||||
## Example-flow function-node fan-out
|
||||
|
||||
### examples/02-Dashboard.json :: `fn_status_split` (outputs: 15)
|
||||
|
||||
| # | Target widget | Payload | Populated | Degraded/null |
|
||||
|---|---|---|---|---|
|
||||
| 0 | ui-text "Mode" | string | ✔ structure | gap |
|
||||
| 1 | ui-text "Direction" | string | ✔ | gap |
|
||||
| 2 | ui-text "Level" | number m | ✔ | gap |
|
||||
| 3 | ui-text "Volume" | number m³ | ✔ | gap |
|
||||
| 4 | ui-text "Volume %" | number % | ✔ | gap |
|
||||
| 5 | ui-text "percControl" | number % | ✔ | gap |
|
||||
| 6 | ui-text "Manual demand" | number m³/h or — | gap | gap |
|
||||
| 7 | ui-chart "Level (m)" | `{topic,payload:number}` or no-msg | ✔ | gap |
|
||||
| 8 | ui-chart "Volume (m³)" | ″ | ✔ | gap |
|
||||
| 9 | ui-chart "Volume %" | ″ | ✔ | gap |
|
||||
| 10 | ui-chart "Flow (m³/h)" — Inflow | ″ | ✔ | gap |
|
||||
| 11 | ui-chart "Flow (m³/h)" — Outflow | ″ | ✔ | gap |
|
||||
| 12 | ui-chart "Flow (m³/h)" — Net | ″ | ✔ | gap |
|
||||
| 13 | ui-template "Raw output table" | whole object (array) | ✔ | gap |
|
||||
| 14 | ui-chart "percControl" | `{topic:'percControl',payload:number}` | ✔ | gap |
|
||||
|
||||
Populated/structure coverage: test/integration/basic-dashboard-flow.test.js
|
||||
(asserts output count = 15 and routes outputs 0–14). **Degraded/empty-input**
|
||||
coverage (no `payload:null` reaching any `ui-chart`) is still a gap — see below.
|
||||
|
||||
## Known coverage gaps (tracked, prospective per the rule)
|
||||
|
||||
The output-coverage rule applies prospectively. Outstanding items for this node:
|
||||
|
||||
- [ ] Dedicated `test/basic/output-port0.test.js` exercising **every** key above
|
||||
in both populated and degraded (pre-tick / null) states.
|
||||
- [ ] Port-1 line-protocol assertion (field names + tag).
|
||||
- [ ] Port-2 `child.register` payload-shape test.
|
||||
- [ ] `fn_status_split` degraded/empty-input fan-out test (no `payload:null` to
|
||||
any `ui-chart`) — the failure mode the rule was written for. The structure
|
||||
test in `basic-dashboard-flow.test.js` covers the populated path only.
|
||||
@@ -35,7 +35,7 @@ test('basic dashboard flow contains the pumpingStation node and trend widgets',
|
||||
assert.equal(ps.inletPipeDiameter, 0.3);
|
||||
assert.equal(ps.outletPipeDiameter, 0.3);
|
||||
assert.ok(parser, 'fn_status_split should exist');
|
||||
assert.equal(parser.outputs, 14);
|
||||
assert.equal(parser.outputs, 15);
|
||||
assert.equal(levelChart.type, 'ui-chart');
|
||||
assert.equal(volumeChart.type, 'ui-chart');
|
||||
assert.equal(flowChart.type, 'ui-chart');
|
||||
@@ -72,7 +72,7 @@ test('basic dashboard parser routes process fields to charts and state text', ()
|
||||
}, context, node);
|
||||
|
||||
assert.ok(Array.isArray(out));
|
||||
assert.equal(out.length, 14);
|
||||
assert.equal(out.length, 15);
|
||||
assert.equal(out[0].payload, 'levelbased');
|
||||
assert.equal(out[1].payload, 'filling');
|
||||
assert.equal(out[2].payload, '3.25 m');
|
||||
@@ -86,6 +86,7 @@ test('basic dashboard parser routes process fields to charts and state text', ()
|
||||
assert.deepEqual(out[11], { topic: 'Outflow', payload: 7.2 });
|
||||
assert.deepEqual(out[12], { topic: 'Net', payload: 10.8 });
|
||||
assert.ok(Array.isArray(out[13].payload));
|
||||
assert.deepEqual(out[14], { topic: 'percControl', payload: 25 });
|
||||
});
|
||||
|
||||
test('basic dashboard parser keeps previous values when process output sends only changed fields', () => {
|
||||
|
||||
@@ -1,6 +1,6 @@
|
||||
# Reference — Contracts
|
||||
|
||||
 
|
||||
 
|
||||
|
||||
> [!NOTE]
|
||||
> Full topic contract, configuration schema, and child-registration filters for `pumpingStation`. The topic-contract and data-model sections are **regenerated by `npm run wiki:all`** — do not hand-edit between the `BEGIN AUTOGEN` / `END AUTOGEN` markers. Source of truth for everything on this page: the node's `src/commands/index.js`, `src/specificClass.js` `configure()`, and the schema at `generalFunctions/src/configs/pumpingStation.json`.
|
||||
@@ -19,11 +19,11 @@ The **Unit** column reflects each descriptor's `units: { measure, default }` dec
|
||||
|---|---|---|---|---|
|
||||
| `set.mode` | `changemode` | `string` | — | Switch the station between auto / manual control modes. |
|
||||
| `child.register` | `registerChild` | `string` | — | Register a child node (machine group, measurement, …) with this station. |
|
||||
| `cmd.calibrate.volume` | `calibratePredictedVolume` | any | `volume` (default `m3`) | Calibrate the predicted-volume integrator to a known basin volume. |
|
||||
| `cmd.calibrate.level` | `calibratePredictedLevel` | any | `length` (default `m`) | Calibrate the predicted-volume integrator to a known basin level. |
|
||||
| `set.inflow` | `q_in` | any | `volumeFlowRate` (default `m3/h`) | Push a measured inflow value into the basin balance. |
|
||||
| `set.outflow` | `q_out` | any | `volumeFlowRate` (default `m3/h`) | Push a measured outflow value into the basin balance. |
|
||||
| `set.demand` | `Qd` | any | `volumeFlowRate` (default `m3/h`) | Operator outflow demand setpoint for the station. |
|
||||
| `cmd.calibrate.volume` | `calibratePredictedVolume` | `any` | `volume` (default `m3`) | Calibrate the predicted-volume integrator to a known basin volume. |
|
||||
| `cmd.calibrate.level` | `calibratePredictedLevel` | `any` | `length` (default `m`) | Calibrate the predicted-volume integrator to a known basin level. |
|
||||
| `set.inflow` | `q_in` | `any` | `volumeFlowRate` (default `m3/h`) | Push a measured inflow value into the basin balance. |
|
||||
| `set.outflow` | `q_out` | `any` | `volumeFlowRate` (default `m3/h`) | Push a measured outflow value into the basin balance. |
|
||||
| `set.demand` | `Qd` | `any` | `volumeFlowRate` (default `m3/h`) | Operator outflow demand setpoint for the station. |
|
||||
|
||||
<!-- END AUTOGEN: topic-contract -->
|
||||
|
||||
@@ -39,35 +39,42 @@ Keys composed each tick by `specificClass.getOutput()` and emitted via `outputUt
|
||||
|---|---|---|---|
|
||||
| `direction` | string | — | `"steady"` |
|
||||
| `dryRunLevel` | number | — | `0.20400000000000001` |
|
||||
| `dryRunSafetyVol` | number | — | `0.20400000000000001` |
|
||||
| `dryRunSafetyVol` | number | — | `2.55` |
|
||||
| `flowSource` | null | — | `null` |
|
||||
| `heightBasin` | number | m | `1` |
|
||||
| `highVolumeSafetyLevel` | number | — | `2.45` |
|
||||
| `highVolumeSafetyVol` | number | — | `2.45` |
|
||||
| `inflowLevel` | number | m | `2` |
|
||||
| `heightBasin` | number | m | `4` |
|
||||
| `highVolumeSafetyLevel` | number | — | `3.7239999999999998` |
|
||||
| `highVolumeSafetyVol` | number | — | `46.55` |
|
||||
| `inflowLevel` | number | m | `1.5` |
|
||||
| `inletPipeDiameter` | number | — | `0.4` |
|
||||
| `maxVol` | number | m3 | `1` |
|
||||
| `maxVolAtOverflow` | number | m3 | `2.5` |
|
||||
| `manualDemand` | null | — | `null` |
|
||||
| `maxVol` | number | m3 | `50` |
|
||||
| `maxVolAtOverflow` | number | m3 | `47.5` |
|
||||
| `minHeightBasedOn` | string | — | `"outlet"` |
|
||||
| `minVol` | number | m3 | `0.2` |
|
||||
| `minVolAtInflow` | number | m3 | `2` |
|
||||
| `minVolAtOutflow` | number | m3 | `0.2` |
|
||||
| `minVol` | number | m3 | `2.5` |
|
||||
| `minVolAtInflow` | number | m3 | `18.75` |
|
||||
| `minVolAtOutflow` | number | m3 | `2.5` |
|
||||
| `mode` | string | — | `"levelbased"` |
|
||||
| `outflowLevel` | number | m | `0.2` |
|
||||
| `outletPipeDiameter` | number | — | `0.4` |
|
||||
| `overflowLevel` | number | m | `2.5` |
|
||||
| `overflowLevel` | number | m | `3.8` |
|
||||
| `percControl` | number | % | `0` |
|
||||
| `predictedOverflowRate` | number | — | `0` |
|
||||
| `predictedOverflowVolume` | number | — | `0` |
|
||||
| `predictedUnderflowVolume` | number | — | `0` |
|
||||
| `surfaceArea` | number | m2 | `1` |
|
||||
| `surfaceArea` | number | m2 | `12.5` |
|
||||
| `timeleft` | null | s | `null` |
|
||||
| `volEmptyBasin` | number | m3 | `1` |
|
||||
| `volume.predicted.atequipment.wikigen-pumpingstation-id` | number | m3 | `0.2` |
|
||||
| `volEmptyBasin` | number | m3 | `50` |
|
||||
| `volume.predicted.atequipment.wikigen-pumpingstation-id` | number | m3 | `2.5` |
|
||||
|
||||
<!-- END AUTOGEN: data-model -->
|
||||
|
||||
Sample values come from a stub instantiation in `wikiGen` — in a live deployment the volume key is shaped `volume.<variant>.<position>.<childId>` per the standard [Measurement Key Shape](https://gitea.wbd-rd.nl/RnD/EVOLV/wiki/Topic-Conventions#measurement-key-shape).
|
||||
|
||||
> [!NOTE]
|
||||
> Two control-state keys carry the live operating mode rather than a measurement:
|
||||
> - `mode` — string, the active control strategy (`levelbased` / `manual` / `flowbased` / `none`). Echoes the most recent `set.mode` input.
|
||||
> - `manualDemand` — number (m³/h) or `null`. The operator outflow setpoint last accepted via `set.demand`; `null` outside `manual` mode.
|
||||
|
||||
---
|
||||
|
||||
## Configuration schema — editor form to config keys
|
||||
|
||||