fix(levelBased): drop hold zone, route through MGC.setDemand, add holdLevel + integrator variant pick; slim npm pack
levelBased ramp + engagement: - Ramp foot is now max(startLevel, holdLevel) — was max(startLevel, inflowLevel). inflowLevel is basin geometry, not a control setpoint; the implicit hold zone it created was causing pumps to "start at inflowLevel" instead of startLevel. - New optional `holdLevel` config (defaults to startLevel = no hold band). When raised, pumps engage at startLevel and hold at 0 % = MGC flow.min across [startLevel, holdLevel], then ramp 0..100 % to maxLevel. - Engagement decided in run() (not in `_applyMachineGroupLevelControl`): rising-edge hysteresis arming gates a clean turnOff early-return. Once armed, the helper always forwards setDemand(pct, '%') — 0 % legitimately means "engaged at min flow", no more soft-turnOff at the boundary. - Disengagement paths (minLevel hard-stop, stopLevel falling-edge, pre-arming idle) now all clear the shifted-ramp hysteresis state too. - Threshold validator drops the startLevel ≤ inflowLevel rule; adds startLevel ≤ holdLevel < maxLevel (only checked when holdLevel is explicitly set, so default-null doesn't false-flag). MGC unit math: - Replace direct group.handleInput(percent) with group.setDemand(pct, '%') in _applyMachineGroupLevelControl. The percent → m³/s resolution now lives in MGC.setDemand (committed separately in the MGC submodule). FlowAggregator variant picking: - New _pickFlowSum() helper mirrors selectBestNetFlow's variant precedence (measured first, then predicted) and resolves each side independently. Realistic mixed case — real measured upstream sensor + predicted pump outflow — now feeds the predicted-volume integrator. Was reading only `flow.predicted.*` so a real upstream sensor (which writes `flow.measured.*`) never moved the level. Editor: - New `holdLevel` and `deadZoneKeepAlivePercent` defaults + side-panel input rows in the levelbased mode preview. - Add the missing `ps-mode-line-holdLevel` SVG marker (was declared in the side-panel coupling but the SVG element didn't exist, so the dashed line never rendered). - Relax stopLevel marker gate so it renders for any non-negative typed value — start/stop ordering is the ribbon's job, not the marker's (was hiding the line whenever startLevel was momentarily smaller). - Add holdLevel to the marker loop in mode-preview so changes track. - Add stopLevel + holdLevel + maxLevel to all three bindRedraw lists (basin-diagram, mode-preview, bounds.apply) so the SVG, validation ribbon, and HTML5 min/max attrs update on every edit. - Initialise stopLevel + holdLevel + deadZoneKeepAlivePercent inputs in oneditprepare so reopening the editor shows the saved values. - nodeClass passes holdLevel + deadZoneKeepAlivePercent into the domain config. Tests: - New test/basic/_probe_upstream_emit.test.js: confirms the parent surfaces flow.measured.upstream.* on Port 0 after a measurement child write — pins the previously-invisible measured variant flow. - flowAggregator.basic.test.js: two new regression cases — measured inflow when predicted side is empty, and the measured-in / predicted-out mixed case. - control-levelBased.basic.test.js: new cases for the holdLevel hold band, the [stopLevel, startLevel] keep-alive, the engagement gate, and the "0 % at startLevel = setDemand" contract. - specificClass.test.js: zone tests adjusted to the new ramp foot. Shifted-ramp tests pin holdLevel = 3 explicitly so their legacy arithmetic (ramp foot at inflowLevel) stays self-consistent. - shifted-ramp-end-to-end.test.js: same holdLevel pin for the same reason. Packaging: - Add .gitignore + .npmignore so the published tarball drops the wiki/, simulations/, test/, tools/, .claude/ etc. The pack went from 1.5 MB (72 files) to ~57 KB (30 files). Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
This commit is contained in:
@@ -86,6 +86,8 @@
|
||||
shiftArmPercent: { value: 95 },
|
||||
startLevel: { value: 1 }, // m, pump-on threshold (engagement edge)
|
||||
stopLevel: { value: 0.5 }, // m, pump-off threshold (hysteresis fall-back)
|
||||
holdLevel: { value: 1 }, // m, ramp 0%-foot; defaults to startLevel (= no hold zone)
|
||||
deadZoneKeepAlivePercent: { value: 1 }, // % emitted across [stopLevel, startLevel] keep-alive band
|
||||
minLevel: { value: 0.3 }, // m, hard-stop (just above outflow pipe top)
|
||||
maxLevel: { value: 3.8 }, // m, 100% demand saturation
|
||||
flowSetpoint: { value: null },
|
||||
@@ -418,6 +420,11 @@
|
||||
<input type="number" id="node-input-stopLevel" min="0" step="0.01" />
|
||||
<span class="ps-unit">m</span>
|
||||
</div>
|
||||
<div class="ps-row" data-stroke="#27AE60" data-couples-line="ps-mode-line-holdLevel">
|
||||
<div><label>holdLevel</label><div class="ps-sub">0 % ramp foot — leave at startLevel for no hold band</div></div>
|
||||
<input type="number" id="node-input-holdLevel" min="0" step="0.01" />
|
||||
<span class="ps-unit">m</span>
|
||||
</div>
|
||||
<div class="ps-row ps-readonly" data-stroke="#1F4E79" data-couples-line="ps-mode-line-inflowLevel">
|
||||
<div><label>inflowLevel</label><div class="ps-sub">from basin above</div></div>
|
||||
<span id="ps-mode-readout-inflow" class="ps-readonly-val">— m</span>
|
||||
@@ -475,6 +482,7 @@
|
||||
<line id="ps-mode-line-dryRunLevel" y1="24" y2="140" stroke="#C0392B" stroke-dasharray="2 2" />
|
||||
<line id="ps-mode-line-startLevel" y1="24" y2="140" stroke="#1E8449" stroke-dasharray="2 2" />
|
||||
<line id="ps-mode-line-stopLevel" y1="24" y2="140" stroke="#7D3C98" stroke-dasharray="2 2" />
|
||||
<line id="ps-mode-line-holdLevel" y1="24" y2="140" stroke="#27AE60" stroke-dasharray="2 2" />
|
||||
<line id="ps-mode-line-inflowLevel" y1="24" y2="140" stroke="#1F4E79" stroke-dasharray="2 2" />
|
||||
<line id="ps-mode-line-maxLevel" y1="24" y2="140" stroke="#D68910" stroke-dasharray="2 2" />
|
||||
<line id="ps-mode-line-overflowLevel" y1="24" y2="140" stroke="#C0392B" stroke-dasharray="2 2" />
|
||||
|
||||
Reference in New Issue