Add eval harness + Tier 2/3 mode template pages ### eval/ (scenario-based evaluation) Complements the unit tests under test/basic. Scenarios fluctuate inputs over simulated time, record every tick to JSONL, print a summary table + event log, and check expectations. Complementary to unit tests — these answer "how does the system respond to this input profile" rather than "is this function correct". - eval/run.js — driver; monkey-patches Date.now so the volume integrator ticks at 1 s/iter regardless of wall-clock - eval/scenarios/ — one file per scenario - levelbased-steady.js — constant inflow, demand converges - levelbased-storm.js — inflow surge, demand saturates - safety-dry-run-trip.js — manual mode, empty basin, safety trips - eval/formatters/table.js — ASCII summary of sampled ticks - eval/logs/ — per-scenario JSONL output (one line per tick) - eval/README.md — usage + scenario file shape + how to pipe into InfluxDB/Grafana All three starter scenarios PASS with their expectations. ### wiki/modes/ (tier template pages) The levelbased page templated Tier-1 modes (static transfer function). Added worked examples for the other two tiers so all mode pages share a common skeleton and new modes have something concrete to imitate: - flowbased.md — Tier 2 (PID on measured outflow) - powerbased.md — Tier 2 (levelbased curve clipped by grid power budget) - mpc.md — Tier 3 (optimisation + forecast; block diagram + scenario time-series instead of a fixed curve) - modes/README.md — updated with the three-tier classification table and diagram-type-per-tier guidance Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-04-22 16:49:41 +02:00
---
title: Flow-based mode
mode: flowbased
tier: 2
status: placeholder
updated: 2026-04-22
---
# Flow-based mode — *Tier 2 template*
> **Status — not yet implemented.** The `flowbased` entry is a placeholder in `_controlLogic`. This page reserves the shape and documents the intended design so all Tier-2 modes share the same layout.
## At a glance
| Item | Value |
|---|---|
| Tier | 2 — parameterised transfer function |
| Signal driving demand | measured outflow (actual pumps) |
| Secondary inputs | integrator + derivative state (for PID) |
| Output | demand 0100 % via PID correction |
| Thresholds adjusted at runtime? | No (but the demand can move independently of level) |
| Use when | The station has a flow sensor on the outlet and you want to hold a target outflow rate regardless of basin level |
## Diagram
**Primary plot.** Demand vs *outflow-error* (not level!) is the meaningful transfer function for flow-based control. The curve is a classic PID surface — proportional slope times error, plus integral + derivative terms.
**Secondary plot.** Level still enters as gates (STOP below `minLevel`, don't overfill above `maxLevel`) — same thresholds as levelbased, but the mode doesn't *use* level to pick demand.
```
Placeholder image — replace with:
diagrams/modes/flowbased.drawio.svg (demand vs outflow-error, showing Kp slope)
```
## Inputs
| Signal | Where from | Role |
|---|---|---|
| measured outflow | sum of `flow.measured.*` at outflow positions | error = (flowSetpoint measuredOutflow) |
| `config.control.flowBased.flowSetpoint` | editor, static | target outflow in m³/h |
| `config.control.flowBased.flowDeadband` | editor, static | zone around setpoint where PID output holds |
| `config.control.flowBased.pid.{kp, ki, kd, ...}` | editor / schema | PID gains + rate limits |
| current level | fallback → threshold gates | only used for `minLevel`/`maxLevel` bounds |
## Threshold policy
The **control** thresholds (`minLevel`, `startLevel`, `maxLevel`) are still enforced but for different reasons than levelbased:
| Threshold | Role in flowbased |
|---|---|
| `minLevel` | If level drops below, force demand=0 regardless of PID output (prevents pump undercut) |
| `startLevel` | unused — demand is driven by error, not level |
| `maxLevel` | If level climbs above, force demand=100 regardless of PID output (prevents spill) |
## Demand formula
```text
error = flowSetpoint measuredOutflow
if level < minLevel:
demand = 0 # pump-undercut guard
elif level > maxLevel:
demand = 100 # anti-spill guard
else:
# normal PID branch
P = Kp × error
I += Ki × error × dt # with anti-windup clamp
D = Kd × d(error)/dt # with low-pass filter
demand = clamp(P + I + D, 0, 100) # with rate limits Δup/Δdown
```
## Edge cases
- **Cold start, no prior outflow measurement.** PID state starts at 0; first error is `flowSetpoint`. Integral term will build up — rate-limit the demand ramp to avoid over-shoot.
- **Sensor dropout on the outflow meter.** Fall back to predicted outflow (sum of pump curve predictions). Log a warning — PID on predicted-only is unreliable.
- **Setpoint step change.** PID with derivative filter + rate limits handles this gracefully; without filter, the D-kick would saturate output.
- **Safety layer interaction.** Same as levelbased — `dryRunLevel` and `overflowLevel` override the PID output. See [functional description § Safety](../functional-description.md#safety-controller).
## Related
- [Functional description](../functional-description.md) — basin model + shared safety layer
- [modes/README.md](README.md) — mode index + page template
- [modes/levelbased.md](levelbased.md) — Tier 1 reference implementation