PS calls turnOffAllMachines on every tick once level < stopLevel. Two ways the pump could re-engage after we shut it down: 1. _delayedCall: a 1% dead-zone keep-alive parked in MGC's deferred dispatch fires from the in-flight handleInput's finally block AFTER the shutdown completes, dispatching flow + startup to a fresh pump. Clear _delayedCall at the top of turnOff. 2. Concurrent shutdown calls on the same pump interrupt each other before the sequence can transition past stopping. Track shutdown- in-flight per pump and skip if one is already underway. Together with the rotatingMachine delayedMove-clearing fix, this lets the level-based hysteresis cycle complete: pumps shut off cleanly at stopLevel, basin reverses direction, refills to startLevel, repeat. Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>