Rene De Ren a14aa0dab8 handleInput: skip abort+redispatch when demand unchanged
Live trace showed PS ticking every 1 s and re-firing the SAME demand
(100% saturated under storm inflow) while the basin level evolved slowly.
Each tick was calling abortActiveMovements + optimalControl, which
aborted in-flight pump moves before they could finish (move duration
~0.4 s vs 1 s tick) and immediately re-issued the same setpoint. Pumps
got stuck ramping from the same starting position toward the same
target indefinitely — moveTimeleft stable at 0.379 s for minutes,
flow.predicted frozen.

Now early-return when |demandQ - prev| < max(0.5, prev*0.005). PS
hysteresis float jitter is filtered, real demand changes still
propagate. Pumps finish their first move and stay at the right
setpoint instead of being aborted forever.