handlePressureChange: mirror aggregate flow onto DOWNSTREAM
PS subscribes to MGC's flow.predicted.downstream and uses it as the outflow estimate for net-flow computation. MGC was only writing to DOWNSTREAM inside optimalControl (the optimizer's bestFlow TARGET, not the achieved aggregate), and to AT_EQUIPMENT in handlePressureChange. During transients — e.g. demand dropping to dead-band keep-alive while pumps are still ramping down from full throttle — PS saw a stale 25 m³/h target on DOWNSTREAM while pumps were physically delivering 500+ m³/h. NetFlow looked small and stable when the basin was actually draining fast. flow.act = sum of every pump's current predicted output = achieved aggregate. Mirror it onto DOWNSTREAM so PS gets a live signal on every pump flow/pressure update, not just every MGC.handleInput. Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
This commit is contained in:
@@ -283,6 +283,18 @@ class MachineGroup {
|
||||
|
||||
this.logger.debug(`Dynamic Totals after pressure change - Flow: Min ${flow.min}, Max ${flow.max}, Act ${flow.act} | Power: Min ${power.min}, Max ${power.max}, Act ${power.act}`);
|
||||
this._writeMeasurement("flow", "predicted", POSITIONS.AT_EQUIPMENT, flow.act, this.unitPolicy.canonical.flow);
|
||||
// Mirror the aggregate flow onto DOWNSTREAM as well. PS subscribes to
|
||||
// flow.predicted.downstream from MGC and uses it as the outflow
|
||||
// estimate for net-flow computation. Without this mirror, the only
|
||||
// place DOWNSTREAM gets written is optimalControl's bestFlow (the
|
||||
// optimizer's TARGET, not the achieved aggregate). During transients
|
||||
// — e.g. demand dropping to dead-band keep-alive while pumps are
|
||||
// still ramping down from full throttle — PS would see a stale
|
||||
// 25 m³/h target while pumps are physically delivering 500+ m³/h,
|
||||
// making netFlow look small and stable when the basin is actually
|
||||
// draining fast. flow.act here is the sum of every pump's current
|
||||
// predicted output, so it IS the achieved aggregate.
|
||||
this._writeMeasurement("flow", "predicted", POSITIONS.DOWNSTREAM, flow.act, this.unitPolicy.canonical.flow);
|
||||
this._writeMeasurement("power", "predicted", POSITIONS.AT_EQUIPMENT, power.act, this.unitPolicy.canonical.power);
|
||||
|
||||
const { maxEfficiency, lowestEfficiency } = this.calcGroupEfficiency(this.machines);
|
||||
|
||||
Reference in New Issue